Density Test Report

Date :02/27/2024
Project No :2023C141
Client Company :Toll Bros
Arrival Time :02/27/2024 15:00
Onsite Hours :02:30
Name of the Project :N. Gate - Old Atlanta Road
Project Location :Cumming
Weather :cloudy
Departure Time :02/27/2024 17:30
ASEC Technician Name :Aminullah Azimi

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
02/27/2024 1 18.8 102.3 24469 103.9 18.7 98.5 95 D6938 Pass
Location : Lot #33, Elv/Depth :9 feet below finished grade
Comment : Gauge Serial No. :85759
02/27/2024 2 22.4 100.5 24469 103.9 18.7 96.7 95 D6938 Pass
Location : Basement of Lot #33, Elv/Depth :2.5 feet below finished grade
Comment : Gauge Serial No. :85759
02/27/2024 3 16.8 108.7 24468 111.3 17.5 97.7 95 D6938 Pass
Location : Water storm, 22 feet west of MH 2A.1, Elv/Depth :2 feet below finished grade
Comment : Gauge Serial No. :85759
02/27/2024 4 20.6 101.2 24469 103.9 18.7 97.4 95 D6938 Pass
Location : Water storm, 25 feet east of MH 2A.2, Elv/Depth :3 feet below finished grade
Comment : Gauge Serial No. :85759
Technician Signature / DateAminullah Azimi, February 27, 2024
Reviewer Name / DateKenneth Mosman, March 16, 2024