Skip to content

Density Test Report

Date :03/04/2024
Project No :2023C141
Client Company :Toll Bros
Arrival Time :03/04/2024 9:00
Onsite Hours :04:00
Name of the Project :N. Gate - Old Atlanta Road
Project Location :Cumming
Weather :cloudy
Departure Time :03/04/2024 13:00
ASEC Technician Name :Aminullah Azimi

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
03/04/2024 1 16.3 103.8 24469 103.9 18.7 99.9 95 D6938 Pass
Location : Lot #33, Elv/Depth :7 feet below finished grade
Comment : Gauge Serial No. :85759
03/04/2024 2 16.9 106.8 24468 111.3 17.5 96.0 95 D6938 Pass
Location : Lot #34, Elv/Depth :6 feet below finished grade
Comment : Gauge Serial No. :85759
Technician Signature / DateAminullah Azimi, March 4, 2024
Reviewer Name / DateKenneth Mosman, March 17, 2024