Density Test Report

Date :03/04/2024
Project No :2022C165
Client Company :Toll Bros. Inc.
Arrival Time :03/04/2024 13:00
Onsite Hours :03:00
Name of the Project :Northfield @ Polo Fields - Phase2
Project Location :Pittman Road, Cumming, GA
Weather :cloudy
Departure Time :03/04/2024 16:00
ASEC Technician Name :Aminullah Azimi

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
03/04/2024 1 27.2 91.4 4 98.6 20.2 92.7 90 D6938 Pass
Location : 77 feet south of SS MH A4, Elv/Depth :5 feet below finished grade
Comment : Moisture content more than 3 percent over optimum moisture content Gauge Serial No. :85759
03/04/2024 2 28.1 87.7 2 95.0 23.5 92.3 90 D6938 Pass
Location : 110 feet north of SS MH A3, Elv/Depth :6 feet below finished grade
Comment : Moisture content more than 3 percent over optimum moisture content Gauge Serial No. :85759
Technician Signature / DateAminullah Azimi, March 4, 2024
Reviewer Name / DateKenneth Mosman, March 17, 2024