- Density Test Report Report ID: 65086
- Edit Download Report
Density Test Report
Date :03/14/2024
Project No :2023C141
Client Company :Toll Bros
Arrival Time :03/14/2024 13:00
Onsite Hours :02:00
Name of the Project :N. Gate - Old Atlanta Road
Project Location :Cumming
Weather :sunny
Departure Time :03/14/2024 15:00
ASEC Technician Name :Aminullah Azimi
Observations/Finding
Test Date | Test Number | Moisture Content (%) | Dry Density (pcf) | Proctor Number | Max. Dry Density (pcf) | Optimum Moisture (%) | Compaction (%) | Specified Compaction (%) | ASTM Test Method | Pass/Fail |
---|---|---|---|---|---|---|---|---|---|---|
03/14/2024 | 1 | 19.6 | 106.0 | 24468 | 111.3 | 17.5 | 95.2 | 95 | D6938 | Pass |
Location : | Lot #31, Elv/Depth :7 feet below finished grade | |||||||||
Comment : | Gauge Serial No. :85759 | |||||||||
03/14/2024 | 2 | 20.6 | 104.1 | 24469 | 103.9 | 18.7 | 100.2 | 90 | D6938 | Pass |
Location : | Lot #31, basement , Elv/Depth :finished grade | |||||||||
Comment : | Gauge Serial No. :85759 | |||||||||
03/14/2024 | 3 | 17.6 | 103.2 | 24469 | 103.9 | 18.7 | 99.3 | 90 | D6938 | Pass |
Location : | Lot #31, Elv/Depth :6 feet below finished grade | |||||||||
Comment : | Gauge Serial No. :85759 |
Technician Signature / DateAminullah Azimi, March 14, 2024
Reviewer Name / DateKenneth Mosman, March 28, 2024