Density Test Report

Date :03/18/2024
Project No :2023C141
Client Company :Toll Bros
Arrival Time :03/18/2024 10:00
Onsite Hours :03:30
Name of the Project :N. Gate - Old Atlanta Road
Project Location :Cumming
Weather :sunny
Departure Time :03/18/2024 13:30
ASEC Technician Name :Aminullah Azimi

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
03/18/2024 1 16.3 103.4 24469 103.9 18.7 99.5 90 D6938 Pass
Location : Lot #31, Elv/Depth :5.5 feet below finished grade
Comment : Gauge Serial No. :85759
03/18/2024 2 15.7 102.5 24469 103.9 18.7 98.7 95 D6938 Pass
Location : Lot #31, Elv/Depth :5.5 below finished grade
Comment : Gauge Serial No. :85759
Technician Signature / DateAminullah Azimi, March 18, 2024
Reviewer Name / DateKenneth Mosman, March 28, 2024