- Density Test Report Report ID: 65611
- Edit Download Report
Density Test Report
Date :03/29/2024
Project No :2022C165
Client Company :Toll Bros. Inc.
Arrival Time :03/29/2024 8:30
Onsite Hours :07:00
Name of the Project :Northfield @ Polo Fields - Phase2
Project Location :Pittman Road, Cumming, GA
Weather :Sunny
Departure Time :03/29/2024 15:30
ASEC Technician Name :Fawad Shagiwal
Observations/Finding
Test Date | Test Number | Moisture Content (%) | Dry Density (pcf) | Proctor Number | Max. Dry Density (pcf) | Optimum Moisture (%) | Compaction (%) | Specified Compaction (%) | ASTM Test Method | Pass/Fail |
---|---|---|---|---|---|---|---|---|---|---|
03/29/2024 | 1 | 27.7 | 93.0 | 2 | 95.0 | 23.5 | 97.9 | 95 | D6938 | Pass |
Location : | MSE Retaining wall at the vicinity of lot# 27, Elv/Depth :4.5 feet above MSE Retaining wall | |||||||||
Comment : | Gauge Serial No. :3430 | |||||||||
03/29/2024 | 2 | 19.3 | 100.2 | 3 | 99.4 | 21.3 | 100.8 | 95 | D6938 | Pass |
Location : | MSE Retaining wall at the vicinity of lot# 28, Elv/Depth :4.5 feet above MSE Retaining wall | |||||||||
Comment : | Gauge Serial No. :3430 |
Technician Signature / DateFawad Shagiwal, March 29, 2024
Reviewer Name / DateKenneth Mosman, April 23, 2024