Density Test Report

Date :03/29/2024
Project No :2023C141
Client Company :Toll Bros
Arrival Time :03/29/2024 9:00
Onsite Hours :07:00
Name of the Project :N. Gate - Old Atlanta Road
Project Location :Cumming
Weather :sunny
Departure Time :03/29/2024 16:00
ASEC Technician Name :Aminullah Azimi

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
03/29/2024 1 18.3 101.7 24469 103.9 18.7 97.9 95 D6938 Pass
Location : Lot #35, Elv/Depth :4 feet below finished grade
Comment : Gauge Serial No. :85759
03/29/2024 2 17.1 103.4 24469 103.9 18.7 99.5 95 D6938 Pass
Location : Lot #35 basement , Elv/Depth :finished grade
Comment : Gauge Serial No. :85759
03/29/2024 3 20.2 100.9 24469 103.9 18.7 97.1 95 D6938 Pass
Location : Lot #35, Elv/Depth :3 feet below finished grade
Comment : Gauge Serial No. :85759
03/29/2024 4 19.2 100.3 24469 103.9 18.7 96.5 95 D6938 Pass
Location : Lot #51, Elv/Depth :4 feet below finished grade
Comment : Gauge Serial No. :85759
03/29/2024 5 20.4 106.3 24468 111.3 17.5 95.5 95 D6938 Pass
Location : Lot #51 , Elv/Depth :2.5 feet below finished grade
Comment : Gauge Serial No. :85759
03/29/2024 6 17.5 103.1 24469 103.9 18.7 99.2 95 D6938 Pass
Location : Lot #35, Elv/Depth :2 feet below finished grade
Comment : Gauge Serial No. :85759
Technician Signature / DateAminullah Azimi, March 29, 2024
Reviewer Name / DateKenneth Mosman, April 23, 2024