Density Test Report

Date :04/02/2024
Project No :2023C141
Client Company :Toll Bros
Arrival Time :04/01/2024 8:00
Onsite Hours :04:00
Name of the Project :N. Gate - Old Atlanta Road
Project Location :Cumming
Weather :sunny
Departure Time :04/01/2024 12:00
ASEC Technician Name :Aminullah Azimi

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
04/01/2024 1 15.3 100.9 24469 103.9 18.7 97.1 95 D6938 Pass
Location : Lot #35, Elv/Depth :finished grade
Comment : Moisture content higher than 3 percent over optimum moisture Gauge Serial No. :85759
04/01/2024 2 15.8 105.9 24468 111.3 17.5 95.1 95 D6938 Pass
Location : Lot #51 basement., Elv/Depth :finished grade
Comment : Gauge Serial No. :85759
04/02/2024 3 15.3 100.9 24469 103.9 18.7 97.1 95 D6938 Pass
Location : Lot #51, Elv/Depth :3.5 feet below finished grade
Comment : Moisture content higher than 3 percent over optimum moisture Gauge Serial No. :85759
Technician Signature / DateAminullah Azimi, April 2, 2024
Reviewer Name / DateKenneth Mosman, April 25, 2024