- Density Test Report Report ID: 65810
- Edit Download Report
Density Test Report
Date :04/05/2024
Project No :2023C141
Client Company :Toll Bros
Arrival Time :04/05/2024 09:00
Onsite Hours :07:00
Name of the Project :N. Gate - Old Atlanta Road
Project Location :Cumming
Weather :Sunny
Departure Time :04/05/2024 16:00
ASEC Technician Name :Fawad Shagiwal
Observations/Finding
Test Date | Test Number | Moisture Content (%) | Dry Density (pcf) | Proctor Number | Max. Dry Density (pcf) | Optimum Moisture (%) | Compaction (%) | Specified Compaction (%) | ASTM Test Method | Pass/Fail |
---|---|---|---|---|---|---|---|---|---|---|
04/05/2024 | 01 | 17.2 | 97.3 | 24469 | 103.9 | 18.7 | 93.6 | 90 | D6938 | Pass |
Location : | Ditch behind Lot #53, Elv/Depth :4 feet below finished grade | |||||||||
Comment : | Gauge Serial No. :3430 | |||||||||
04/05/2024 | 02 | 24.6 | 93.9 | 24469 | 103.9 | 18.7 | 90.4 | 90 | D6938 | Pass |
Location : | Ditch behind the Lot #52, Elv/Depth :4 feet below finished grade | |||||||||
Comment : | Gauge Serial No. :3430 |
Technician Signature / DateFawad Shagiwal, April 5, 2024
Reviewer Name / DateKenneth Mosman, April 25, 2024