Density Test Report

Date :04/26/2024
Project No :2024C112
Client Company :SR Homes
Arrival Time :04/26/2024
Onsite Hours :
Name of the Project :Sterlington
Project Location :Canton
Weather :overcast
Departure Time :04/26/2024
ASEC Technician Name :Russell Hendrix

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
04/26/2024 1 27.5 79.5 P-01 94.8 25.0 83.9 98 D6938 Fail
Location : 10 feet south of A6, Elv/Depth :-1 foot from finished
Comment : Recommended scarify and recompaction Gauge Serial No. :30942
04/26/2024 1 18.2 105.0 P-01 94.8 25.0 93.7 95 D6938 Fail
Location : Lot #10, Elv/Depth :- 3 feet from finished
Comment : recommended additional compaction Gauge Serial No. :30942
04/26/2024 Re-test #1 19.5 94.3 P-01 94.8 25.0 99.5 95 D6938 Pass
Location : Lot #10, Elv/Depth :-3 feet from finished
Comment : Gauge Serial No. :30942
04/26/2024 Re-test #2 18.8 95.5 P-01 94.8 25.0 100.7 95 D6938 Pass
Location : Lot #11, Elv/Depth :- 3 feet from finished
Comment : Gauge Serial No. :30942
Technician Signature / DateRussell Hendrix, April 26, 2024
Reviewer Name / DateKenneth Mosman, May 23, 2024