Density Test Report

Date :12/04/2024
Project No :2024C202
Client Company :CCG
Arrival Time :12/04/2024 07:15
Onsite Hours :
Name of the Project :Old Griffin Rd - Hawthorne Reserve
Project Location :Dallas
Weather :Sunny
Departure Time :
ASEC Technician Name :Solomon Cherie

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
12/04/2024 1 25.7 87.1 S-02 97.2 24.9 89.6 95 D6938 Fail
Location : Access road, Elv/Depth :3 feet below finished grade
Comment : This area needs to be recompacted. Observed noticable pumping/rutting under dump truck traffic. Gauge Serial No. :30942
12/04/2024 2 24.7 93.3 S-02 97.2 24.9 96.0 95 D6938 Pass
Location : Access road, Elv/Depth :3 feet below finished grade
Comment : Gauge Serial No. :30942
12/04/2024 3 25.4 94.3 S-02 97.2 24.9 97.0 95 D6938 Pass
Location : Access road, Elv/Depth :1.5 feet below finished grade
Comment : Gauge Serial No. :30942
12/04/2024 4 24.6 94.5 S-02 97.2 24.9 97.2 95 D6938 Pass
Location : Access road, Elv/Depth :2 feet below finished grade
Comment : Gauge Serial No. :30942
Technician Signature / DateSolomon Cherie, December 4, 2024
Reviewer Name / DateKenneth Mosman, January 10, 2025