- Home
- Density Test Report Report ID: 76383
- This project is inactive from admin. Download Report
Density Test Report
Date :01/23/2025
Project No :2024C168
Client Company :Century Communities
Arrival Time :01/23/2025 10:30
Onsite Hours :07:00
Name of the Project :Reserve @ Gum Springs
Project Location :Jefferson, Jackson County, Georgia
Weather :sunny
Departure Time :01/23/2025 17:30
ASEC Technician Name :Aminullah Azimi
Observations/Finding
| Test Date | Test Number | Moisture Content (%) | Dry Density (pcf) | Proctor Number | Max. Dry Density (pcf) | Optimum Moisture (%) | Compaction (%) | Specified Compaction (%) | ASTM Test Method | Pass/Fail |
|---|---|---|---|---|---|---|---|---|---|---|
| 01/23/2025 | 454 | 5.6 | 137.2 | 27651 | 143.6 | 5.4 | 95.5 | 92 | D6938 | Pass |
| Location : | Retaining wall #1 backfill at station 0+95, Elv/Depth :4 feet below finished grade | |||||||||
| Comment : | Gauge Serial No. :85759 | |||||||||
| 01/23/2025 | 455 | 5.9 | 136.3 | 27651 | 143.6 | 5.4 | 94.9 | 92 | D6938 | Pass |
| Location : | Retaining wall #1 backfill at station 0+55, Elv/Depth :3.5 feet below finished grade | |||||||||
| Comment : | Gauge Serial No. :85759 | |||||||||
| 01/23/2025 | 456 | 2.4 | 137.9 | 27651 | 143.6 | 5.4 | 96.0 | 92 | D6938 | Pass |
| Location : | Retaining wall #1 backfill at station 0+15, Elv/Depth :2.5 feet below finished grade | |||||||||
| Comment : | Gauge Serial No. :85759 | |||||||||
| 01/23/2025 | 457 | 5.7 | 135.0 | 27651 | 143.6 | 5.4 | 94.0 | 92 | D6938 | Pass |
| Location : | Retaining wall #2 backfill at station 1+70, Elv/Depth :1.5 feet below finished grade | |||||||||
| Comment : | Gauge Serial No. :85759 | |||||||||
| 01/23/2025 | 458 | 6 | 136.0 | 27651 | 143.6 | 5.4 | 94.7 | 92 | D6938 | Pass |
| Location : | Retaining wall #1 backfill at station 0+90, Elv/Depth :3 feet below finished grade | |||||||||
| Comment : | Gauge Serial No. :85759 | |||||||||
| 01/23/2025 | 459 | 5.2 | 136.2 | 27651 | 143.6 | 5.4 | 94.8 | 92 | D6938 | Pass |
| Location : | Retaining wall #1 backfill at station 0+50, Elv/Depth :3 feet below finished grade | |||||||||
| Comment : | Gauge Serial No. :85759 | |||||||||
| 01/23/2025 | 460 | 4.2 | 138.1 | 27651 | 143.6 | 5.4 | 96.2 | 92 | D6938 | Pass |
| Location : | Retaining wall #1 backfill at station 0+20, Elv/Depth :1.5 feet below finished grade | |||||||||
| Comment : | Gauge Serial No. :85759 | |||||||||
Technician Signature / DateAminullah Azimi, January 23, 2025
Reviewer Name / DateKenneth Mosman, January 26, 2025