Density Test Report

Date :04/21/2025
Project No :2025C160
Client Company :Artisan
Arrival Time :04/21/2025 09:00
Onsite Hours :
Name of the Project :Rockmart Township - 115 Felton Drive
Project Location :Rockmart
Weather :
Departure Time :04/21/2025
ASEC Technician Name :Solomon Cherie

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
04/21/2025 1 16.3 105.8 2025-012 SP 105.6 18.9 100.2 95 D6938 Pass
Location : Sewer line ssmh 1.0A, Elv/Depth :1 foot below finished grade
Comment : Gauge Serial No. :30942
04/21/2025 2 16.6 102.7 2025-012 SP 105.6 18.9 97.3 95 D6938 Pass
Location : Ssmh 1.0B, Elv/Depth :1 foot below finished grade
Comment : Gauge Serial No. :30942
04/21/2025 3 16.9 109.4 2025-011 SP 115.0 15.5 95.1 95 D6938 Pass
Location : Lot #39, Elv/Depth :at finished subgrade
Comment : Gauge Serial No. :30942
04/21/2025 4 15.3 111.1 2025-008 SP 115.7 14.7 96.0 95 D6938 Pass
Location : Lot #124, Elv/Depth :at finished subgrade
Comment : Gauge Serial No. :30942
04/21/2025 5 19.2 104.8 2025-012 SP 105.6 18.9 99.2 95 D6938 Pass
Location : Lot #122, Elv/Depth :at finished subgrade
Comment : Gauge Serial No. :30942
04/21/2025 6 14.1 113.4 2025-011 SP 115.0 15.5 98.6 95 D6938 Pass
Location : Lot #121, Elv/Depth :at finished subgrade
Comment : Gauge Serial No. :30942
04/21/2025 07 19.8 103.2 2025-012 SP 105.6 18.9 97.7 95 D6938 Pass
Location : Lot #117, Elv/Depth :at finished subgrade
Comment : Gauge Serial No. :30942
Technician Signature / DateSolomon Cherie, April 21, 2025
Reviewer Name / DateKenneth Mosman, May 03, 2025