Density Test Report

Date :04/17/2025
Project No :2024C213
Client Company :WDG
Arrival Time :04/17/2025 8:00
Onsite Hours :9:30
Name of the Project :Covington Town Center PH II
Project Location :Covington, GA
Weather :sunny
Departure Time :04/17/2025 17:30
ASEC Technician Name :Aminullah Azimi

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
04/17/2025 1 17.7 103.7 ASECP001 106.0 18.2 97.8 95 D6938 Pass
Location : storm trench, between MHA0 and MHB1, Elv/Depth :2 feet below finished grade
Comment : Gauge Serial No. :85759
04/17/2025 2 16.2 95.3 2025-017 SP 99.0 18.3 96.3 95 D6938 Pass
Location : service line, in front of building, Elv/Depth :3 feet below finished grade
Comment : Gauge Serial No. :85759
04/17/2025 3 16.7 103.6 ASECP001 106.0 18.2 97.7 95 D6938 Pass
Location : sewer trench, 25 feet to the east from existing MH, Elv/Depth :1.5 feet below finished grade
Comment : Gauge Serial No. :85759
04/17/2025 4 19.2 95.6 2025-017 SP 99.0 18.3 96.6 95 D6938 Pass
Location : water storm trench, between MHB1 and MH B2, Elv/Depth :2.5 feet below finished grade
Comment : Gauge Serial No. :85759
04/17/2025 5 16.5 103.9 ASECP001 106.0 18.2 98.0 95 D6938 Pass
Location : water storm trench, between MHB2 and MHB3, Elv/Depth :1.5 feet below finished grade
Comment : Gauge Serial No. :85759
04/17/2025 6 16.9 104.4 ASECP001 106.0 18.2 98.5 95 D6938 Pass
Location : water storm trench, between MHB3 and MHB4, Elv/Depth :1 foot below finished grade
Comment : Gauge Serial No. :85759
04/17/2025 7 17.6 103.8 ASECP001 106.0 18.2 97.9 95 D6938 Pass
Location : water storm trench, 78 feet below to the west from MHD1, Elv/Depth :1.5 feet below finished grade
Comment : Gauge Serial No. :85759
04/17/2025 8 20.1 94.4 28586 98.7 20.6 95.6 95 D6938 Pass
Location : water storm trench, 16 feet to the SW from MHB1, Elv/Depth :1.5 feet below finished grade
Comment : Gauge Serial No. :85759
04/17/2025 9 17.1 105.0 ASECP001 106.0 18.2 99.1 95 D6938 Pass
Location : water storm trench, between MHA0 and MHB1, Elv/Depth :at finished grade
Comment : Gauge Serial No. :85759
04/17/2025 10 17.2 120.1 ASECP001 106.0 18.2 96.7 95 D6938 Pass
Location : service line, in the front of building , Elv/Depth :2 feet below finished grade
Comment : Gauge Serial No. :85759
Technician Signature / DateAminullah Azimi, April 17, 2025
Reviewer Name / DateKenneth Mosman, May 04, 2025