Density Test Report

Date :05/16/2025
Project No :2024C213
Client Company :WDG
Arrival Time :05/16/2025 7:30
Onsite Hours :04:30
Name of the Project :Covington Town Center PH II
Project Location :Covington, GA
Weather :cloudy
Departure Time :05/16/2025 12:00
ASEC Technician Name :Aminullah Azimi

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
05/16/2025 1 30 88.5 ASECP001 106.0 18.2 83.5 95 D6938 Fail
Location : Retaining wall B, station 0+25, Elv/Depth :1 foot below finished grade
Comment : In-situ moisture contents much higher than optimum. Recommended scarify, aerate and recompaction. Gauge Serial No. :85759
05/16/2025 2 29.5 88.6 ASECP001 106.0 18.2 83.6 95 D6938 Fail
Location : retaining wall B, station 0+75, Elv/Depth :1 foot below finished grade
Comment : In-situ moisture contents much higher than optimum. Recommended scarify, aerate and recompaction. Gauge Serial No. :85759
Technician Signature / DateAminullah Azimi, May 16, 2025
Reviewer Name / DateKenneth Mosman, June 09, 2025