- Density Test Report Report ID: 82017
- This project is inactive from admin. Download Report
Density Test Report
Date :06/07/2025
Project No :2025C160
Client Company :Artisan
Arrival Time :06/07/2025 08:30
Onsite Hours :
Name of the Project :Rockmart Township - 115 Felton Drive
Project Location :Rockmart
Weather :
Departure Time :
ASEC Technician Name :Solomon Cherie
Observations/Finding
| Test Date | Test Number | Moisture Content (%) | Dry Density (pcf) | Proctor Number | Max. Dry Density (pcf) | Optimum Moisture (%) | Compaction (%) | Specified Compaction (%) | ASTM Test Method | Pass/Fail |
|---|---|---|---|---|---|---|---|---|---|---|
| 06/07/2025 | 1 | 20.7 | 99.3 | 2025-012 SP | 105.6 | 18.9 | 94.0 | 98 | D6938 | Fail |
| Location : | Lot #15, Elv/Depth :At finished grade | |||||||||
| Comment : | This area requires recompaction and retesting. | Gauge Serial No. :30942 | ||||||||
| 06/07/2025 | 2 | 19.6 | 97.1 | 2025-012 SP | 105.6 | 18.9 | 92.0 | 98 | D6938 | Fail |
| Location : | Lot #16, Elv/Depth :At finished grade | |||||||||
| Comment : | This area requires recompaction and retesting. | Gauge Serial No. :30942 | ||||||||
| 06/07/2025 | 3 | 19.3 | 101.3 | 2025-012 SP | 105.6 | 18.9 | 95.9 | 98 | D6938 | Fail |
| Location : | Lot #17, Elv/Depth :At finished grade | |||||||||
| Comment : | This area requires recompaction and retesting. | Gauge Serial No. :30942 | ||||||||
| 06/07/2025 | 4 | 20.1 | 102.2 | 2025-012 SP | 105.6 | 18.9 | 96.8 | 98 | D6938 | Fail |
| Location : | Lot #18, Elv/Depth :At finished grade | |||||||||
| Comment : | This area requires recompaction and retesting. | Gauge Serial No. :30942 | ||||||||
| 06/07/2025 | 5 | 20.3 | 105.4 | 2025-011 SP | 115.0 | 15.5 | 91.7 | 95 | D6938 | Fail |
| Location : | Lot #129, Elv/Depth :3 feet below finished grade | |||||||||
| Comment : | High moisture contents. This area requires scarifying/aeration prior to recompaction and retesting. | Gauge Serial No. :30942 | ||||||||
| 06/07/2025 | 6 | 22.4 | 98.4 | 2025-012 SP | 105.6 | 18.9 | 93.2 | 95 | D6938 | Fail |
| Location : | Lot #130, Elv/Depth :3 feet below finished grade | |||||||||
| Comment : | High moisture contents. This area requires scarifying/aeration prior to recompaction and retesting. | Gauge Serial No. :30942 | ||||||||
Technician Signature / DateSolomon Cherie, June 7, 2025
Reviewer Name / DateKenneth Mosman, June 09, 2025