Density Test Report

Date :05/19/2025
Project No :2025C160
Client Company :Artisan
Arrival Time :05/19/2025 07:30
Onsite Hours :08:00
Name of the Project :Rockmart Township - 115 Felton Drive
Project Location :Rockmart
Weather :sunny
Departure Time :05/19/2025 15:30
ASEC Technician Name :Sean Willett

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
05/19/2025 1 24.2 95.1 2025-012 SP 105.6 18.9 90.1 98 D2937 Fail
Location : SSMH4.0 , Elv/Depth :finial grade
Comment : In-situ moisture content well over optimum moisture. Recommended scarify, aerate and recompact.
05/19/2025 2 20.8 103.0 2025-012 SP 105.6 18.9 97.5 98 D2937 Fail
Location : SSMH4.0, Elv/Depth :finial grade
Comment :
05/19/2025 3 24.2 0.0 2025-012 SP 105.6 18.9 0.0 D2937 Pass
Location : Lot #112, Elv/Depth :
Comment : Moisture content check on potential fill material.
05/19/2025 4 20.5 0.0 2025-012 SP 105.6 18.9 0.0 D2937 Pass
Location : lot 116, Elv/Depth :
Comment : Moisture content check on potential fill material.
05/19/2025 5 20.6 0.0 2025-012 SP 105.6 18.9 0.0 D2937 Pass
Location : lot 116, Elv/Depth :
Comment : Moisture content check on potential fill material.
Technician Signature / DateSean Willett, May 19, 2025
Reviewer Name / DateKenneth Mosman, June 23, 2025