Density Test Report

Date :05/20/2025
Project No :2025C160
Client Company :Artisan
Arrival Time :05/20/2025 07:30
Onsite Hours :07:00
Name of the Project :Rockmart Township - 115 Felton Drive
Project Location :Rockmart
Weather :sunny
Departure Time :05/20/2025 14:30
ASEC Technician Name :Sean Willett

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
05/20/2025 1 26.1 86.7 2025-012 SP 105.6 18.9 82.1 95 D2937 Fail
Location : Lot #82, Elv/Depth :4 feet below finished grade
Comment : In-situ moisture contents well above optimum moisture. Recommend aerating this area and recompact once site is drier.
05/20/2025 2 19.0 101.1 2025-012 SP 105.6 18.9 95.7 95 D2937 Pass
Location : Lot #84, Elv/Depth :4 feet below finished grade
Comment :
05/20/2025 3 22.3 95.4 2025-012 SP 105.6 18.9 90.3 95 D2937 Fail
Location : Lot #82, Elv/Depth :2 feet below finished grade
Comment : In-situ moisture contents above optimum moisture. Recommend aerating this area and recompact once site is drier.
05/20/2025 4 25.2 93.5 2025-012 SP 105.6 18.9 88.5 95 D2937 Fail
Location : Lot #84, Elv/Depth :2 feet below finished grade
Comment : In-situ moisture contents well above optimum moisture. Recommend aerating this area and recompact once site is drier.
Technician Signature / DateSean Willett, May 20, 2025
Reviewer Name / DateKenneth Mosman, June 23, 2025