Density Test Report

Date :06/03/2025
Project No :2024C213
Client Company :WDG
Arrival Time :06/03/2025 08:30
Onsite Hours :01:30
Name of the Project :Covington Town Center PH II
Project Location :Covington, GA
Weather :overcast
Departure Time :06/03/2025 10:00
ASEC Technician Name :Sean Willett

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
06/03/2025 1 24.3 89.6 ASECP001 106.0 18.2 84.5 90 D2937 Fail
Location : Left side on retaining wall located along main road, Elv/Depth :2 feet below finished grade
Comment : In-situ moisture contents well above optimum. Recommended that these materials be removed, spread out and aerated to reduce moisture content.
06/03/2025 2 26.0 87.1 ASECP001 106.0 18.2 82.2 90 D2937 Fail
Location : Middle of retaining wall located along main road, Elv/Depth :2 feet below finished grade
Comment : In-situ moisture contents well above optimum. Recommended that these materials be removed, spread out and aerated to reduce moisture content.
06/03/2025 3 23.1 89.9 ASECP001 106.0 18.2 84.8 90 D2937 Fail
Location : Right side of retaining wall located along main road, Elv/Depth :2 feet below finished grade
Comment : In-situ moisture contents well above optimum. Recommended that these materials be removed, spread out and aerated to reduce moisture content.
06/03/2025 4 28.2 84.1 ASECP001 106.0 18.2 79.3 90 D2937 Fail
Location : Left side of retaining wall located on building pad, Elv/Depth :2 feet below finished grade
Comment : In-situ moisture contents well above optimum. Recommended that these materials be removed, spread out and aerated to reduce moisture content.
06/03/2025 5 25.2 84.6 ASECP001 106.0 18.2 79.8 90 D2937 Fail
Location : Middle of retaining wall located on building pad, Elv/Depth :2 feet below finished grade
Comment : In-situ moisture contents well above optimum. Recommended that these materials be removed, spread out and aerated to reduce moisture content.
06/03/2025 6 27.7 83.1 ASECP001 106.0 18.2 78.4 90 D2937 Fail
Location : Right side of retaining wall located on building pad, Elv/Depth :2 feet below finished grade
Comment : In-situ moisture contents well above optimum. Recommended that these materials be removed, spread out and aerated to reduce moisture content.
Technician Signature / DateSean Willett, June 3, 2025
Reviewer Name / DateKenneth Mosman, July 17, 2025