Density Test Report

Date :06/20/2025
Project No :2025C160
Client Company :Artisan
Arrival Time :06/20/2025 11:00
Onsite Hours :02:30
Name of the Project :Rockmart Township - 115 Felton Drive
Project Location :Rockmart
Weather :sunny
Departure Time :06/20/2025 13:30
ASEC Technician Name :Sean Willett

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
06/20/2025 1 21.5 102.4 2025-012 SP 105.6 18.9 97.0 95 D6938 Pass
Location : Lot #167, Elv/Depth :791.5
Comment : Gauge Serial No. :38069
06/20/2025 2 19.6 120.1 2025-012 SP 105.6 18.9 95.1 95 D6938 Pass
Location : Lot #167, Elv/Depth :791.5
Comment : Gauge Serial No. :38069
06/20/2025 3 18.7 107.6 2025-012 SP 105.6 18.9 101.9 95 D6938 Pass
Location : Lot #170, Elv/Depth :791.5
Comment : Gauge Serial No. :38069
06/20/2025 4 19.3 107.2 2025-012 SP 105.6 18.9 101.5 95 D6938 Pass
Location : Lot #170, Elv/Depth :791.5
Comment : Gauge Serial No. :38069
Technician Signature / DateSean Willett, June 20, 2025
Reviewer Name / DateKenneth Mosman, August 06, 2025