Density Test Report

Date :06/27/2025
Project No :2025C160
Client Company :Artisan
Arrival Time :06/27/2025 08:30
Onsite Hours :
Name of the Project :Rockmart Township - 115 Felton Drive
Project Location :Rockmart
Weather :Overcast
Departure Time :06/27/2025
ASEC Technician Name :Sean Willett

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
06/27/2025 1 18.3 103.7 2025-012 SP 105.6 18.9 Check
Location : Lot #39, Elv/Depth :775.5 (at finished grade)
Comment : Proctor check 2025-012 SP
06/27/2025 2 18.9 101.8 2025-025 SP 104.5 13.2 97.4 98 D2937 Fail
Location : Lot #39, Elv/Depth :775.5 (at finished grade)
Comment :
Technician Signature / DateSean Willett, June 27, 2025
Reviewer Name / DateKenneth Mosman, August 06, 2025