Density Test Report

Date :07/09/2025
Project No :2025C160
Client Company :Artisan
Arrival Time :07/09/2025 10:30
Onsite Hours :04:00
Name of the Project :Rockmart Township - 115 Felton Drive
Project Location :Rockmart
Weather :Partly cloudy
Departure Time :07/09/2025 14:30
ASEC Technician Name :Austin Coleman

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
07/09/2025 1 26.6 90.4 Field proctor 0 Check
Location : Lower lots, Elv/Depth :at finished grade
Comment :
07/09/2025 2 20 92.4 2025-025 SP 104.5 13.2 88.4 95 D6938 Fail
Location : Lower lots (west side), Elv/Depth :3 feet below finished grade
Comment : Measured at 95% compaction on the field proctor (possibly a different material) Gauge Serial No. :
07/09/2025 3 20 93.7 2025-012 SP 105.6 18.9 88.7 95 D6938 Fail
Location : Lower lots (east side), Elv/Depth :3 feet below finished grade
Comment : Hit at 95.8% compaction on the field proctor Gauge Serial No. :
Technician Signature / DateAustin Coleman, July 9, 2025
Reviewer Name / DateKenneth Mosman, August 07, 2025