Density Test Report

Date :07/11/2025
Project No :2025C160
Client Company :Artisan
Arrival Time :07/11/2025 09:00
Onsite Hours :
Name of the Project :Rockmart Township - 115 Felton Drive
Project Location :Rockmart
Weather :Sunny
Departure Time :07/11/2025
ASEC Technician Name :Sean Willett

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
07/11/2025 1 19.7 93.3 2025-012 SP 105.6 18.9 88.4 95 D2937 Fail
Location : Lot #155, Elv/Depth :6 feet below finished grade
Comment : Recompaction required
07/11/2025 2 17.6 94.4 2025-012 SP 105.6 18.9 89.4 95 D2937 Fail
Location : Lot #166, Elv/Depth :4 feet below finished grade
Comment : Recompaction required
Technician Signature / DateSean Willett, July 11, 2025
Reviewer Name / DateKenneth Mosman, August 07, 2025