Density Test Report

Date :07/14/2025
Project No :2025C160
Client Company :Artisan
Arrival Time :07/14/2025 08:30
Onsite Hours :
Name of the Project :Rockmart Township - 115 Felton Drive
Project Location :Rockmart
Weather :Sunny
Departure Time :07/14/2025
ASEC Technician Name :Sean Willett

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
07/14/2025 1 14.0 98.5 2025-012 SP 105.6 18.9 Check
Location : Approximately Lot #166, Elv/Depth :6 feet below finished grade
Comment : Proctor check on fill, (compares on the dry side of proctor 2025-012 SP optimum moisture content
Technician Signature / DateSean Willett, July 14, 2025
Reviewer Name / DateKenneth Mosman, August 08, 2025