Density Test Report

Date :08/20/2025
Project No :2025C215
Client Company :Artisan
Arrival Time :08/20/2025 09:30
Onsite Hours :07:30
Name of the Project :NW Unit 4 Parkway Ext. Phase 1
Project Location :Dallas
Weather :Sunny
Departure Time :08/20/2025 17:00
ASEC Technician Name :Safiullah Momand

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
08/20/2025 1 19 90.5 2025-032 SP 94.9 25.0 95.4 95 D6938 Pass
Location : 35 feet away from manhole 8 toward manhole 9 , Elv/Depth :9 feet below finished grade
Comment : Gauge Serial No. :3430
08/20/2025 2 16.7 94.1 2025-032 SP 94.9 25.0 99.2 95 D6938 Pass
Location : 80 feet away from manhole 8 toward manhole 9 , Elv/Depth :9 feet below finished grade
Comment : Gauge Serial No. :3430
08/20/2025 3 24 93.9 2025-032 SP 94.9 25.0 98.9 95 D6938 Pass
Location : 130 feet away from Manhole 9 toward Manhole 8, Elv/Depth :9 feet below finished grade
Comment : Gauge Serial No. :3430
08/20/2025 4 20.9 93.5 2025-032 SP 94.9 25.0 98.5 95 D6938 Pass
Location : 60 feet away from Manhole 9 toward Manhole 8, Elv/Depth :9 feet below finished grade
Comment : Gauge Serial No. :3430
Technician Signature / DateSafiullah Momand, August 20, 2025
Reviewer Name / DateKenneth Mosman, September 12, 2025