Density Test Report

Date :08/25/2025
Project No :2025C215
Client Company :Artisan
Arrival Time :08/25/2025 9:00
Onsite Hours :07:30
Name of the Project :NW Unit 4 Parkway Ext. Phase 1
Project Location :Dallas
Weather :sunny
Departure Time :08/25/2025 16:30
ASEC Technician Name :Aminullah Azimi

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
08/25/2025 1 19.1 118.7 2025-033 SP 104.0 16.2 95.9 95 D6938 Pass
Location : Sewer trench 112 feet to the east of MH8, Elv/Depth :at finished grade
Comment : Gauge Serial No. :30942
08/25/2025 2 22.1 92.5 2025-032 SP 94.9 25.0 97.5 95 D6938 Pass
Location : Sewer trench 151 feet to the west of MH6, Elv/Depth :at finished grade
Comment : Gauge Serial No. :30942
08/25/2025 3 18 97.0 2025-031 SP 101.0 20.7 96.0 95 D6938 Pass
Location : Sewer trench 52 feet to the west of MH6, Elv/Depth :2 Feet below finished grade
Comment : Gauge Serial No. :30942
08/27/2025 4 17.3 96.3 2025-031 SP 101.0 20.7 95.3 95 D6938 Pass
Location : Sewer trench 3 feet to the west of MH6, Elv/Depth :6 feet below finished grade
Comment : Gauge Serial No. :30942
08/25/2025 5 18.5 96.2 2025-031 SP 101.0 20.7 95.2 95 D6938 Pass
Location : Between MH6 and MH6A, Elv/Depth :6 Feet below finished grade
Comment : Gauge Serial No. :30942
08/25/2025 6 24.2 90.3 2025-032 SP 94.9 25.0 95.2 95 D6938 Pass
Location : Water storm trench between Headwall C1 and MHC2, Elv/Depth :10 feet below finished grade
Comment : Gauge Serial No. :30942
Technician Signature / DateAminullah Azimi, August 25, 2025
Reviewer Name / DateKenneth Mosman, September 12, 2025