Density Test Report

Date :09/02/2025
Project No :2025C160
Client Company :Artisan
Arrival Time :09/02/2025 08:00
Onsite Hours :07:30
Name of the Project :Rockmart Township - 115 Felton Drive
Project Location :Rockmart
Weather :Sunny/overcast
Departure Time :09/02/2025 15:30
ASEC Technician Name :Sean Willett

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
09/02/2025 1 14.1 117.9 2025-008 SP 115.7 14.7 101.9 98 D6938 Pass
Location : Lot #172, Elv/Depth :792
Comment : Gauge Serial No. :77-19952
09/02/2025 2 17.7 102.5 2025-025 SP 104.5 13.2 98.1 98 D6938 Pass
Location : Lot #182, Elv/Depth :at finished grade
Comment : Gauge Serial No. :77-19952
09/02/2025 3 14.2 94.0 2025-012 SP 105.6 18.9 89.0 98 D6938 Fail
Location : Lot #181, Elv/Depth :at finished grade
Comment : Recommend recompaction of this area. Contractor agreed. Gauge Serial No. :77-19952
09/02/2025 4 15.3 96.2 2025-012 SP 105.6 18.9 91.1 98 D6938 Fail
Location : Lot #181, Elv/Depth :at finished grade
Comment : Recommend recompaction of this area. Contractor agreed. Gauge Serial No. :77-19952
09/02/2025 5 25.1 117.8 2025-012 SP 105.6 18.9 89.2 98 D6938 Fail
Location : Lot #180, Elv/Depth :at finished grade
Comment : High in-situ moisture content. Recommend scarify, aerate and recompaction of this area. Contractor agreed. Gauge Serial No. :77-19952
Technician Signature / DateSean Willett, September 2, 2025
Reviewer Name / DateKenneth Mosman, September 17, 2025