Density Test Report

Date :10/03/2025
Project No :2025C245
Client Company :Bearing Engineering
Arrival Time :10/03/2025 08:00
Onsite Hours :06:00
Name of the Project :Dunkin Donuts 2025
Project Location :US 29, Palmetto, GA
Weather :Sunny
Departure Time :10/03/2025 14:00
ASEC Technician Name :Sean Willett

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
10/03/2025 1 14.3 97.4 2 103.6 17.1 94.0 95 D6938 Fail
Location : Testing location #4 on retaining wall, Elv/Depth :7 feet below finished grade
Comment : Recompaction is required. Gauge Serial No. :77-19952
10/03/2025 2 14.1 95.4 2 103.6 17.1 92.1 95 D6938 Fail
Location : Test location #5 on retaining wall, Elv/Depth :7 feet below finished grade
Comment : Recompaction is required. Gauge Serial No. :77-19952
10/03/2025 3 15.6 90.2 2 103.6 17.1 87.1 95 D6938 Fail
Location : Test location #6 on retaining wall, Elv/Depth :7 feet below finished grade
Comment : Recompaction is required. Gauge Serial No. :77-19952
10/03/2025 4 16 95.9 2 103.6 17.1 92.6 95 D6938 Fail
Location : Test location #6 (Retest), Elv/Depth :7 feet below finished grade
Comment : Recompaction required. Gauge Serial No. :77-19952
Technician Signature / DateSean Willett, October 3, 2025
Reviewer Name / DateKenneth Mosman, October 13, 2025