Density Test Report

Date :10/06/2025
Project No :2025C245
Client Company :Bearing Engineering
Arrival Time :10/06/2025 07:00
Onsite Hours :07:00
Name of the Project :Dunkin Donuts 2025
Project Location :US 29, Palmetto, GA
Weather :Overcast
Departure Time :10/06/2025 14:00
ASEC Technician Name :Sean Willett

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
10/06/2025 1 17.4 83.5 2 103.6 17.1 80.6 95 D6938 Fail
Location : Test location #1 on retaining wall, Elv/Depth :5 feet below finished grade
Comment : Recompaction required. Gauge Serial No. :77-19952
10/06/2025 2 14.4 93.8 2 103.6 17.1 90.5 95 D6938 Fail
Location : Testing location #2 along retaining wall, Elv/Depth :5 feet below finished grade
Comment : Recompaction required. Gauge Serial No. :77-19952
10/06/2025 3 17.5 92.9 2 103.6 17.1 89.7 95 D6938 Fail
Location : Testing location #6 along retaining wall, Elv/Depth :5 feet below finished grade
Comment : Recompaction required. Gauge Serial No. :77-19952
10/06/2025 4 12.4 101.5 2 103.6 17.1 98.0 95 D6938 Pass
Location : Testing location #5 on retaining wall, Elv/Depth :5 feet below finished grade
Comment : Gauge Serial No. :77-19952
10/06/2025 5 15.4 94.2 2 103.6 17.1 90.9 95 D6938 Fail
Location : Testing location #5 on retaining wall, Elv/Depth :5 feet below finished grade
Comment : Recompaction required. Gauge Serial No. :77-19952
10/06/2025 6 15.9 95.9 2 103.6 17.1 92.6 95 D6938 Fail
Location : Testing location #2 on retaining wall, Elv/Depth :5 feet below finished grade
Comment : Recompaction required. Gauge Serial No. :77-19952
10/06/2025 7 24.1 83.9 3 94.7 25.3 88.6 95 D6938 Fail
Location : Testing location #4 on retaining wall, Elv/Depth :5 feet below finished grade
Comment : Recompaction required. Gauge Serial No. :77-19952
10/06/2025 8 15.6 93.9 2 103.6 17.1 90.6 95 D6938 Fail
Location : Testing location #1 on retaining wall, Elv/Depth :5 feet below finished grade
Comment : Recompaction required. Gauge Serial No. :77-19952
10/06/2025 9 14.8 94.5 2 103.6 17.1 91.2 95 D6938 Fail
Location : Testing location #1 on retaining wall, Elv/Depth :5 feet below finished grade
Comment : Recompaction required. Gauge Serial No. :77-19952
Technician Signature / DateSean Willett, October 6, 2025
Reviewer Name / DateKenneth Mosman, October 13, 2025