- Density Test Report Report ID: 86648
- Edit Download Report
Density Test Report
Date :10/06/2025
Project No :2025C245
Client Company :Bearing Engineering
Arrival Time :10/06/2025 07:00
Onsite Hours :07:00
Name of the Project :Dunkin Donuts 2025
Project Location :US 29, Palmetto, GA
Weather :Overcast
Departure Time :10/06/2025 14:00
ASEC Technician Name :Sean Willett
Observations/Finding
| Test Date | Test Number | Moisture Content (%) | Dry Density (pcf) | Proctor Number | Max. Dry Density (pcf) | Optimum Moisture (%) | Compaction (%) | Specified Compaction (%) | ASTM Test Method | Pass/Fail |
|---|---|---|---|---|---|---|---|---|---|---|
| 10/06/2025 | 1 | 17.4 | 83.5 | 2 | 103.6 | 17.1 | 80.6 | 95 | D6938 | Fail |
| Location : | Test location #1 on retaining wall, Elv/Depth :5 feet below finished grade | |||||||||
| Comment : | Recompaction required. | Gauge Serial No. :77-19952 | ||||||||
| 10/06/2025 | 2 | 14.4 | 93.8 | 2 | 103.6 | 17.1 | 90.5 | 95 | D6938 | Fail |
| Location : | Testing location #2 along retaining wall, Elv/Depth :5 feet below finished grade | |||||||||
| Comment : | Recompaction required. | Gauge Serial No. :77-19952 | ||||||||
| 10/06/2025 | 3 | 17.5 | 92.9 | 2 | 103.6 | 17.1 | 89.7 | 95 | D6938 | Fail |
| Location : | Testing location #6 along retaining wall, Elv/Depth :5 feet below finished grade | |||||||||
| Comment : | Recompaction required. | Gauge Serial No. :77-19952 | ||||||||
| 10/06/2025 | 4 | 12.4 | 101.5 | 2 | 103.6 | 17.1 | 98.0 | 95 | D6938 | Pass |
| Location : | Testing location #5 on retaining wall, Elv/Depth :5 feet below finished grade | |||||||||
| Comment : | Gauge Serial No. :77-19952 | |||||||||
| 10/06/2025 | 5 | 15.4 | 94.2 | 2 | 103.6 | 17.1 | 90.9 | 95 | D6938 | Fail |
| Location : | Testing location #5 on retaining wall, Elv/Depth :5 feet below finished grade | |||||||||
| Comment : | Recompaction required. | Gauge Serial No. :77-19952 | ||||||||
| 10/06/2025 | 6 | 15.9 | 95.9 | 2 | 103.6 | 17.1 | 92.6 | 95 | D6938 | Fail |
| Location : | Testing location #2 on retaining wall, Elv/Depth :5 feet below finished grade | |||||||||
| Comment : | Recompaction required. | Gauge Serial No. :77-19952 | ||||||||
| 10/06/2025 | 7 | 24.1 | 83.9 | 3 | 94.7 | 25.3 | 88.6 | 95 | D6938 | Fail |
| Location : | Testing location #4 on retaining wall, Elv/Depth :5 feet below finished grade | |||||||||
| Comment : | Recompaction required. | Gauge Serial No. :77-19952 | ||||||||
| 10/06/2025 | 8 | 15.6 | 93.9 | 2 | 103.6 | 17.1 | 90.6 | 95 | D6938 | Fail |
| Location : | Testing location #1 on retaining wall, Elv/Depth :5 feet below finished grade | |||||||||
| Comment : | Recompaction required. | Gauge Serial No. :77-19952 | ||||||||
| 10/06/2025 | 9 | 14.8 | 94.5 | 2 | 103.6 | 17.1 | 91.2 | 95 | D6938 | Fail |
| Location : | Testing location #1 on retaining wall, Elv/Depth :5 feet below finished grade | |||||||||
| Comment : | Recompaction required. | Gauge Serial No. :77-19952 | ||||||||
Technician Signature / DateSean Willett, October 6, 2025
Reviewer Name / DateKenneth Mosman, October 13, 2025