Density Test Report

Date :10/07/2025
Project No :2025C245
Client Company :Bearing Engineering
Arrival Time :10/07/2025 08:00
Onsite Hours :06:00
Name of the Project :Dunkin Donuts 2025
Project Location :US 29, Palmetto, GA
Weather :Overcast
Departure Time :10/07/2025 14:00
ASEC Technician Name :Sean Willett

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
10/07/2025 1 23.5 83.1 3 94.7 25.3 87.8 95 D6938 Fail
Location : Test location #2 retaining wall, Elv/Depth :5 feet below finished grade
Comment : Recompaction required. Gauge Serial No. :77-19952
10/07/2025 2 24.4 78.4 3 94.7 25.3 82.8 95 D6938 Fail
Location : Test location #3 retaining wall, Elv/Depth :5 feet below finished grade
Comment : Field proctor: 101.0 @ 19% Gauge Serial No. :77-19952
10/07/2025 3 19.5 89.1 3 94.7 25.3 94.1 95 D6938 Fail
Location : Test location #4 retaining wall, Elv/Depth :5 feet below finished grade
Comment : Gauge Serial No. :77-19952
10/07/2025 4 19.5 86.8 3 94.7 25.3 91.7 95 D6938 Fail
Location : Test location #2 retaining wall (retest), Elv/Depth :5 feet below finished grade
Comment : Recompaction required. In-situ moisture contents not within optimum range. Gauge Serial No. :77-19952
10/07/2025 #5 Moisture check 18.7 0.0 Check
Location : stockpile, Elv/Depth :0
Comment : within optimum range Field proctor: 101.0 @ 19%
10/07/2025 6 24 82.3 2 103.6 17.1 79.4 95 D6938 Fail
Location : testing location #2 retaining wall (retest), Elv/Depth :5 feet below finished grade
Comment : In-situ moisture content well above optimum moisture. Gauge Serial No. :77-19952
10/07/2025 7 19.7 91.5 2 103.6 17.1 88.3 95 D6938 Fail
Location : Testing location #3 retaining wall (retest), Elv/Depth :5 feet below finished grade
Comment : Recompaction required. Gauge Serial No. :77-19952
10/07/2025 8 18.8 89.4 2 103.6 17.1 86.3 95 D6938 Fail
Location : Testing location #6 , Elv/Depth :3 feet below finished grade
Comment : Recompaction required. Gauge Serial No. :77-19952
10/07/2025 9 18.8 88.3 2 103.6 17.1 85.2 95 D6938 Fail
Location : Testing location #5 retaining wall , Elv/Depth :3 feet below finished grade
Comment : Recompaction required. Gauge Serial No. :77-19952
10/07/2025 10 18 97.7 2 103.6 17.1 94.3 95 D6938 Fail
Location : Testing location #4, Elv/Depth :4 feet below finished grade
Comment : Gauge Serial No. :77-19952
10/07/2025 11 12.1 102.1 2 103.6 17.1 98.6 95 D6938 Pass
Location : Testing location #3, Elv/Depth :4 feet below finished grade
Comment : Gauge Serial No. :77-19952
10/07/2025 12 15.5 96.4 2 103.6 17.1 93.1 95 D6938 Fail
Location : Testing location #2 , Elv/Depth :4 feet below finished grade
Comment : Recompaction required. Gauge Serial No. :77-19952
10/07/2025 13 17.4 91.7 2 103.6 17.1 88.5 95 D6938 Fail
Location : Testing location #3, Elv/Depth :3 feet below finished grade
Comment : Recompaction required. Gauge Serial No. :77-19952
10/07/2025 14 18.3 89.1 2 103.6 17.1 86.0 95 D6938 Fail
Location : testing location #5 (retest), Elv/Depth :3.5 feet below finished grade
Comment : Recompaction required. Gauge Serial No. :77-19952
10/07/2025 15 15.6 105.9 2 103.6 17.1 102.2 95 D6938 Pass
Location : testing location #2 retaining wall (retest), Elv/Depth :3.5 feet below finished grade
Comment : Gauge Serial No. :77-19952
10/07/2025 16 16.9 100.8 2 103.6 17.1 97.3 95 D6938 Pass
Location : testing location #2 retaining wall (retest), Elv/Depth :3.5 feet below finished grade
Comment : Gauge Serial No. :77-19952
10/07/2025 17 19.2 95.0 2 103.6 17.1 91.7 95 D6938 Fail
Location : testing location #5 retaining wall (retest), Elv/Depth :3 feet below finished grade
Comment : Recompaction required. Gauge Serial No. :77-19952
10/07/2025 18 15.7 97.3 2 103.6 17.1 93.9 95 D6938 Fail
Location : testing location #3 retaining wall (retest), Elv/Depth :3 feet below finished grade
Comment : Recompaction required. Gauge Serial No. :77-19952
Technician Signature / DateSean Willett, October 7, 2025
Reviewer Name / DateKenneth Mosman, October 13, 2025