Density Test Report

Date :10/11/2025
Project No :2025C245
Client Company :Bearing Engineering
Arrival Time :10/11/2025 07:00
Onsite Hours :07:00
Name of the Project :Dunkin Donuts 2025
Project Location :US 29, Palmetto, GA
Weather :Sunny
Departure Time :10/11/2025 14:00
ASEC Technician Name :Sean Willett

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
10/11/2025 1 26.3 92.9 3 94.7 25.3 98.1 95 D6938 Pass
Location : test location #3 retaining wall, Elv/Depth :at finished grade
Comment : Gauge Serial No. :77-19952
10/11/2025 2 16.6 100.9 2 103.6 17.1 97.4 95 D6938 Pass
Location : test location #3 retaining wall, Elv/Depth :at finished grade
Comment : Gauge Serial No. :77-19952
10/11/2025 3 24.2 84.6 3 94.7 25.3 89.3 95 D6938 Fail
Location : roadway in front of retaining wall, Elv/Depth :4 feet below finished grade
Comment : Recompaction required. Gauge Serial No. :77-19952
10/11/2025 4 29.2 86.1 3 94.7 25.3 90.9 95 D6938 Fail
Location : roadway if front of retaining wall, Elv/Depth :4 feet below finished grade
Comment : In-situ moisture contents higher than optimum. Gauge Serial No. :77-19952
10/11/2025 5 23.8 89.7 3 94.7 25.3 94.7 95 D6938 Fail
Location : roadway in front of retaining wall (retest), Elv/Depth :4 feet below finished grade
Comment : Gauge Serial No. :77-19952
10/11/2025 6 24.3 79.8 3 94.7 25.3 84.3 95 D6938 Fail
Location : roadway in front of retaining wall (retest), Elv/Depth :4 feet below finished grade
Comment : Recompaction required. Gauge Serial No. :77-19952
10/11/2025 7 25.3 87.5 3 94.7 25.3 92.4 95 D6938 Fail
Location : test location #3 retaining wall, Elv/Depth :2 feet below finished grade
Comment : Recompaction required. Gauge Serial No. :77-19952
10/11/2025 8 25.7 87.9 3 94.7 25.3 92.8 95 D6938 Fail
Location : test location #2 retaining wall, Elv/Depth :2.5 feet below finished grade
Comment : Recompaction required. Gauge Serial No. :77-19952
10/11/2025 9 26.2 92.7 3 94.7 25.3 97.9 95 D6938 Pass
Location : test location #3 retaining wall (retest), Elv/Depth :2 feet below finished grade
Comment : Gauge Serial No. :77-19952
10/11/2025 10 25.2 92.7 3 94.7 25.3 97.9 95 D6938 Pass
Location : test location #2 retaining wall (retest), Elv/Depth :2.5 feet below finished grade
Comment : Gauge Serial No. :77-19952
10/11/2025 11 22.9 92.3 3 94.7 25.3 97.5 95 D6938 Pass
Location : test location #3 retaining wall, Elv/Depth :1 foot below finished grade
Comment : Gauge Serial No. :77-19952
10/11/2025 12 24.9 91.7 3 94.7 25.3 96.8 95 D6938 Pass
Location : test location #2 retaining wall, Elv/Depth :2 feet below finished grade
Comment : Gauge Serial No. :77-19952
10/11/2025 13 19.7 88.0 3 94.7 25.3 92.9 95 D6938 Fail
Location : roadway in front of retaining wall (retest), Elv/Depth :4 feet below finished grade
Comment : Recompaction required. In-situ moisture content much lower than optimum. Gauge Serial No. :77-19952
10/11/2025 14 25.1 90.5 3 94.7 25.3 95.6 95 D6938 Pass
Location : roadway in front of retaining wall (retest), Elv/Depth :4 feet below finished grade
Comment : Gauge Serial No. :77-19952
10/11/2025 15 22.5 92.5 3 94.7 25.3 97.7 95 D6938 Pass
Location : roadway in front of retaining wall (retest) , Elv/Depth :4 feet below finished grade
Comment : Gauge Serial No. :77-19952
10/11/2025 16 24.4 86.7 3 94.7 25.3 91.6 95 D6938 Fail
Location : test location #1 retaining wall, Elv/Depth :3 feet below finished grade
Comment : Recompaction required. Gauge Serial No. :77-19952
10/11/2025 17 24.8 90.2 3 94.7 25.3 95.2 95 D6938 Pass
Location : test location #1 retaining wall (retest), Elv/Depth :3 feet below finished grade
Comment : Gauge Serial No. :77-19952
Technician Signature / DateSean Willett, October 11, 2025
Reviewer Name / DateKenneth Mosman, October 14, 2025