Density Test Report

Date :11/18/2025
Project No :2025C211
Client Company :Pulte
Arrival Time :11/18/2025 07:30
Onsite Hours :08:00
Name of the Project :Haley's Bluff - Philadelphia Rd.
Project Location :Jasper
Weather :Sunny
Departure Time :11/18/2025 15:30
ASEC Technician Name :Sean Willett

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
11/18/2025 1 15.4 93.5 FP 2 100.0 18.5 93.5 95 D6938 Fail
Location : Lot #4, Elv/Depth :at finished grade
Comment : moisture adjusted with in place dry back moisture due to large amount of mica present in this area. Will retest Gauge Serial No. :77-19952
11/18/2025 2 15.4 100.3 FP 2 100.0 18.5 100.3 95 D6938 Pass
Location : Lot #4 (retest), Elv/Depth :at finished grade
Comment : moisture adjusted with in place dry back moisture due to large amount of mica present in this area. Gauge Serial No. :77-19952
11/18/2025 3 15.4 94.4 FP 2 100.0 18.5 94.4 95 D6938 Fail
Location : Lot #3, Elv/Depth :at finished grade
Comment : moisture adjusted with in place dry back moisture due to large amount of mica present in this area. Will retest Gauge Serial No. :77-19952
11/18/2025 4 15.4 90.1 FP 2 100.0 18.5 90.1 95 D6938 Fail
Location : Lot #3 retest, Elv/Depth :at finished grade
Comment : moisture adjusted with in place dry back moisture due to large amount of mica present in this area. Contractor was informed and will compact again. Will retest again. Gauge Serial No. :77-19952
11/18/2025 5 15.4 91.2 FP 2 100.0 18.5 91.2 95 D6938 Fail
Location : Lot #2, Elv/Depth :at finished grade
Comment : moisture adjusted with in place dry back moisture due to large amount of mica present in this area. Will retest. Gauge Serial No. :77-19952
11/18/2025 6 15.4 90.4 FP 2 100.0 18.5 90.4 95 D6938 Fail
Location : Lot #2 retest, Elv/Depth :at finished grade
Comment : moisture adjusted with in place dry back moisture due to large amount of mica present in this area. Contractor was informed and will recompact. Will retest. Gauge Serial No. :77-19952
11/18/2025 7 15.4 95.2 FP 2 100.0 18.5 95.2 95 D6938 Pass
Location : Lot #1, Elv/Depth :at finished grade
Comment : moisture adjusted with in place dry back moisture due to large amount of mica present in this area. Gauge Serial No. :77-19952
11/18/2025 moisture check 15.4 0.0 Check
Location : Fill placed on Lots #1 through #4 area, Elv/Depth :at finished grade
Comment : moisture check used for gauge moisture adjustment
11/18/2025 8 23.1 93.3 FP 3 100.5 20.5 92.8 95 D6938 Fail
Location : Commercial lots by front detention pond, Elv/Depth :1502
Comment : moisture adjusted with in place dry back moisture due to large amount of mica present in this area. Will retest. Gauge Serial No. :77-19952
11/18/2025 9 22.1 95.6 FP 3 100.5 20.5 95.1 95 D6938 Pass
Location : Commercial lots by front detention pond, Elv/Depth :1502
Comment : Gauge Serial No. :77-19952
11/18/2025 10 19.9 93.8 FP 3 100.5 20.5 93.3 95 D6938 Fail
Location : Commercial lots by front detention pond, Elv/Depth :1502
Comment : will retest Gauge Serial No. :77-19952
11/18/2025 11 23.1 96.0 FP 3 100.5 20.5 95.5 95 D6938 Pass
Location : Commercial lots by front detention pond retest, Elv/Depth :1502
Comment : moisture adjusted with in place dry back moisture due to large amount of mica present in this area. Gauge Serial No. :77-19952
11/18/2025 12 22.4 97.2 FP 3 100.5 20.5 96.7 95 D6938 Pass
Location : Commercial lots by front detention pond retest, Elv/Depth :1502
Comment : Gauge Serial No. :77-19952
11/18/2025 13 15.4 97.9 FP 2 100.0 18.5 97.9 95 D6938 Pass
Location : Lot #2 retest, Elv/Depth :at finished grade
Comment : moisture adjusted with in place dry back moisture due to large amount of mica present in this area. Gauge Serial No. :77-19952
11/18/2025 14 15.4 119.0 FP 3 100.5 20.5 102.6 95 D6938 Pass
Location : Lot #3 retest, Elv/Depth :at finished grade
Comment : moisture adjusted with in place dry back moisture due to large amount of mica present in this area. Gauge Serial No. :77-19952
11/18/2025 15 20.8 91.6 FP 2 100.0 18.5 91.6 95 D6938 Fail
Location : BZ headwall, Elv/Depth :2 to 3 feet over headwall pipeline
Comment : will retest Gauge Serial No. :77-19952
11/18/2025 16 19.9 95.8 FP 3 100.5 20.5 95.3 95 D6938 Pass
Location : BZ headwall pipeline retest, Elv/Depth :2 to 3 feet over pipeline
Comment : Gauge Serial No. :77-19952
11/18/2025 17 19.6 95.5 FP 2 100.0 18.5 95.5 95 D6938 Pass
Location : BZ head wall pipeline, Elv/Depth :2 to 3 feet over pipeline
Comment : Gauge Serial No. :77-19952
11/18/2025 18 14.1 103.7 2025-055 107.3 15.5 96.6 95 D6938 Pass
Location : slope/roadway in front of lot #4 and #5, Elv/Depth :1485
Comment : Gauge Serial No. :77-19952
11/18/2025 19 15.2 106.3 2025-055 107.3 15.5 99.1 95 D6938 Pass
Location : slope/roadway in front of lot 4 and 5, Elv/Depth :1487
Comment : Gauge Serial No. :77-19952
Technician Signature / DateSean Willett, November 18, 2025
Reviewer Name / DateKenneth Mosman, November 24, 2025