- Density Test Report Report ID: 89741
- Edit Download Report
Density Test Report
Date :01/28/2026
Project No :2025C211
Client Company :Pulte
Arrival Time :01/28/2026 08:30
Onsite Hours :07:30
Name of the Project :Haley's Bluff - Philadelphia Rd.
Project Location :Jasper
Weather :Sunny
Departure Time :01/28/2026 16:00
ASEC Technician Name :Sean Willett
Observations/Finding
| Test Date | Test Number | Moisture Content (%) | Dry Density (pcf) | Proctor Number | Max. Dry Density (pcf) | Optimum Moisture (%) | Compaction (%) | Specified Compaction (%) | ASTM Test Method | Pass/Fail |
|---|---|---|---|---|---|---|---|---|---|---|
| 01/28/2026 | 1 | 20.7 | 87.9 | FP 2 | 100.0 | 18.5 | 87.9 | 95 | D6938 | Fail |
| Location : | Retaining wall #5, Elv/Depth :8 baskets | |||||||||
| Comment : | will retest | Gauge Serial No. :77-19952 | ||||||||
| 01/28/2026 | 2 | 18.2 | 89.8 | FP 2 | 100.0 | 18.5 | 89.8 | 95 | D6938 | Fail |
| Location : | Retaining wall #5, Elv/Depth :8 baskets | |||||||||
| Comment : | will retest | Gauge Serial No. :77-19952 | ||||||||
| 01/28/2026 | 3 | 22.4 | 77.7 | FP 2 | 100.0 | 18.5 | 77.7 | 95 | D6938 | Fail |
| Location : | Retaining wall #5, Elv/Depth :8 baskets | |||||||||
| Comment : | contractor placed too thick of a lift. they are cutting it down and recompacting. will retest. | Gauge Serial No. :77-19952 | ||||||||
| 01/28/2026 | 4 | 21.2 | 89.4 | FP 2 | 100.0 | 18.5 | 89.4 | 95 | D6938 | Fail |
| Location : | Retaining wall #5, Elv/Depth :8 baskets | |||||||||
| Comment : | will retest | Gauge Serial No. :77-19952 | ||||||||
| 01/28/2026 | 5 | 17.5 | 95.1 | FP 2 | 100.0 | 18.5 | 95.1 | 95 | D6938 | Pass |
| Location : | Retaining wall #5, Elv/Depth :8 baskets | |||||||||
| Comment : | Gauge Serial No. :77-19952 | |||||||||
| 01/28/2026 | 6 | 19.4 | 89.2 | FP 2 | 100.0 | 18.5 | 89.2 | 95 | D6938 | Fail |
| Location : | Retaining wall #5, Elv/Depth :8 baskets | |||||||||
| Comment : | will retest | Gauge Serial No. :77-19952 | ||||||||
| 01/28/2026 | 7 | 18.6 | 87.9 | FP 2 | 100.0 | 18.5 | 87.9 | 95 | D6938 | Fail |
| Location : | Retaining wall #5, Elv/Depth :8 baskets | |||||||||
| Comment : | will retest | Gauge Serial No. :77-19952 | ||||||||
| 01/28/2026 | 8 | 21.2 | 87.6 | FP 2 | 100.0 | 18.5 | 87.6 | 95 | D6938 | Fail |
| Location : | Retaining wall #5, Elv/Depth :8 baskets | |||||||||
| Comment : | will retest | Gauge Serial No. :77-19952 | ||||||||
| 01/28/2026 | 9 | 20.1 | 90.5 | FP 2 | 100.0 | 18.5 | 90.5 | 95 | D6938 | Fail |
| Location : | Retaining wall #5, Elv/Depth :8 baskets | |||||||||
| Comment : | will retest | Gauge Serial No. :77-19952 | ||||||||
| 01/28/2026 | 10 | 23.0 | 117.6 | FP 3 | 100.5 | 20.5 | 95.1 | 95 | D6938 | Pass |
| Location : | Retaining wall #5, Elv/Depth :8 baskets | |||||||||
| Comment : | Gauge Serial No. :77-19952 | |||||||||
| 01/28/2026 | 11 | 17.0 | 97.8 | FP 2 | 100.0 | 18.5 | 97.8 | 95 | D6938 | Pass |
| Location : | Retaining wall #5, Elv/Depth :9 baskets | |||||||||
| Comment : | Gauge Serial No. :77-19952 | |||||||||
| 01/28/2026 | 12 | 18.5 | 93.2 | FP 2 | 100.0 | 18.5 | 93.2 | 95 | D6938 | Fail |
| Location : | Retaining wall #5, Elv/Depth :9 baskets | |||||||||
| Comment : | will retest | Gauge Serial No. :77-19952 | ||||||||
| 01/28/2026 | 13 | 16.1 | 100.9 | FP 2 | 100.0 | 18.5 | 100.9 | 95 | D6938 | Pass |
| Location : | Retaining wall #5, Elv/Depth :9 baskets | |||||||||
| Comment : | Gauge Serial No. :77-19952 | |||||||||
Technician Signature / DateSean Willett, January 28, 2026
Reviewer Name / DateKenneth Mosman, February 18, 2026