- Density Test Report Report ID: 90876
- Edit Download Report
Density Test Report
Date :02/25/2026
Project No :2025C211
Client Company :Pulte
Arrival Time :02/25/2026 07:00
Onsite Hours :07:30
Name of the Project :Haley's Bluff - Philadelphia Rd.
Project Location :Jasper
Weather :overcast/raining
Departure Time :02/25/2026 14:30
ASEC Technician Name :Sean Willett
Observations/Finding
| Test Date | Test Number | Moisture Content (%) | Dry Density (pcf) | Proctor Number | Max. Dry Density (pcf) | Optimum Moisture (%) | Compaction (%) | Specified Compaction (%) | ASTM Test Method | Pass/Fail |
|---|---|---|---|---|---|---|---|---|---|---|
| 02/25/2026 | 1 | 17.5 | 100.3 | FP 2 | 100.0 | 18.5 | 100.3 | 95 | D6938 | Pass |
| Location : | Lots #30 through 32, Elv/Depth :7 feet below finished grade | |||||||||
| Comment : | Gauge Serial No. :77-19952 | |||||||||
| 02/25/2026 | 2 | 13.6 | 97.1 | FP 2 | 100.0 | 18.5 | 97.1 | 95 | D6938 | Pass |
| Location : | Lots #30 through 32, Elv/Depth :7 feet below finished grade | |||||||||
| Comment : | Gauge Serial No. :77-19952 | |||||||||
| 02/25/2026 | 3 | 15.2 | 97.0 | FP 2 | 100.0 | 18.5 | 97.0 | 95 | D6938 | Pass |
| Location : | Retaining wall #2, Elv/Depth :13 baskets | |||||||||
| Comment : | Gauge Serial No. :77-19952 | |||||||||
| 02/25/2026 | 4 | 20.7 | 99.5 | FP 2 | 100.0 | 18.5 | 99.5 | 95 | D6938 | Pass |
| Location : | Retaining wall #2, Elv/Depth :14 baskets | |||||||||
| Comment : | Gauge Serial No. :77-19952 | |||||||||
| 02/25/2026 | 5 | 20.1 | 99.3 | FP 2 | 100.0 | 18.5 | 99.3 | 95 | D6938 | Pass |
| Location : | Retaining wall #2, Elv/Depth :14 baskets | |||||||||
| Comment : | Gauge Serial No. :77-19952 | |||||||||
| 02/25/2026 | 6 | 18.6 | 99.9 | FP 2 | 100.0 | 18.5 | 99.9 | 98 | D6938 | Pass |
| Location : | SSMH 4.2 to 4.3, Elv/Depth :at finished grade | |||||||||
| Comment : | Gauge Serial No. :77-19952 | |||||||||
| 02/25/2026 | 7 | 16.2 | 103.0 | 2025-055 | 107.3 | 15.5 | 96.0 | 95 | D6938 | Pass |
| Location : | Lots #30 through 32, Elv/Depth :5 feet below finished grade | |||||||||
| Comment : | Gauge Serial No. :77-19952 | |||||||||
| 02/25/2026 | 8 | 16.7 | 99.7 | 2025-055 | 107.3 | 15.5 | 92.9 | 95 | D6938 | Fail |
| Location : | Lots #30 through 32, Elv/Depth :5 feet below finished grade | |||||||||
| Comment : | Gauge Serial No. :77-19952 | |||||||||
| 02/25/2026 | 9 | 20.4 | 99.8 | FP 2 | 100.0 | 18.5 | 99.8 | 95 | D6938 | Pass |
| Location : | Retaining wall #2, Elv/Depth :15 baskets | |||||||||
| Comment : | Gauge Serial No. :77-19952 | |||||||||
| 02/25/2026 | 10 | 16.5 | 95.2 | FP 2 | 100.0 | 18.5 | 95.2 | 95 | D6938 | Pass |
| Location : | Retaining wall #2, Elv/Depth :15 baskets | |||||||||
| Comment : | Gauge Serial No. :77-19952 | |||||||||
Technician Signature / DateSean Willett, February 25, 2026
Reviewer Name / DateKenneth Mosman, March 03, 2026