Density Test Report

Date :04/03/2026
Project No :2025C211
Client Company :Pulte
Arrival Time :04/03/2026 07:30
Onsite Hours :05:00
Name of the Project :Haley's Bluff - Philadelphia Rd.
Project Location :Jasper
Weather :Sunny
Departure Time :04/03/2026 12:30
ASEC Technician Name :Sean Willett

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
04/03/2026 1 14.6 97.1 FP 2 100.0 18.5 97.1 95 D6938 Pass
Location : Retaining wall 1, Elv/Depth :14 baskets
Comment : Gauge Serial No. :77-19952
04/03/2026 2 12.9 92.3 FP 2 100.0 18.5 92.3 95 D6938 Fail
Location : Retaining wall 1, Elv/Depth :14 baskets
Comment : Requires moisture control and recompaction. Gauge Serial No. :77-19952
Technician Signature / DateSean Willett, April 3, 2026
Reviewer Name / DateKenneth Mosman, April 13, 2026