Concrete Test Report

Date :03/31/2026
Project No :2026C115-WO 1
Client Company :WSP
Arrival Time :03/30/2026 21:00
Onsite Hours :12:00
Name of the Project :Lanier Islands Parkway
Project Location :Buford
Weather :Cloudy
Departure Time :03/31/2026 09:00
ASEC Technician Name :Balu Mylabathula

Concrete Placement Information

Location(S): N/A
Testing: 10 Set of concrete specimens (5 per set) were cast during the cast-in-place concrete pour at the above referenced location, in accordance with ASTM C31. The specimen will remain on site for the initial 24-48 hrs curing.
Compliance:

Field placement of concrete appeared to be in accordance with the project specifications (i.e., slump, temperature, etc) (refer to remarks below)

Deviations and/or noncompliances were noted during the field placement (refer to remarks below)

Specimen
Pick Up:
10 Sets of concrete specimens/ 5 specimen per set were picked up & transported to AS Engineering and Consulting LLC (ASEC) for curing and testing in accordance with ASTM C39, C670/1231
Field Curing: Specimen were stored for the initial 24 hours.
Near the poured structure
In an insulated curing box
Other
Remarks:

Field Test Data

Specimen Type Selection : Cylinder

Set Number :A
Date Sampled :03/31/2026
Sampled By :Balu Mylabathula
Contractor :conlan
Truck Number :1
Time Batched :22:45
Location of Placement :N/A
Number of samples cast :5
Ambient Temperature (°f) :N/A
Slump (in.) :4.5
Water added (gal.) :N/A
Laboratory Number :2026-082
Time Sampled :23:00
Weather Condition :Cloudy
Concrete Supplier :morgan
Mix ID :57-89 SOG NA
Quantity of Load (cu. yd.) :10
Sample Cast :10
Specified Strength :4000
Concrete Temperature(°f) :68
Air Content (%) :1.7
Unit Weight (pcf) :148.5

Strength Test Results

Specimen Number Scheduled Test Date Date Tested Age (days) Dia(in.) Area (sq in.) Maximum Loads (lbf) Strength (lbs) % Design Strength Type of Fracture
A1 04/07/2026 04/07/2026 7 3.75 11.04 50547 4580 Infinity Type 5
A2 04/28/2026 04/28/2026 28 3.75 11.04 66936 6060 151.5 Type 2
A3 04/28/2026 04/28/2026 28 3.75 11.04 69084 6260 156.5 Type 5
A4 04/28/2026 04/28/2026 28 3.75 11.04 63753 5770 144.3 Type 3
5 05/26/2026 N/A

UNLESS OTHERWISE SPECIFIED, TESTS WERE PERFORMED IN ACCORDANCE WITH ASTM TEST METHODS C31, C39, C138, C143, C173, AND C1064. FRACTURE TYPE INDICATED BY NUMBER.

(Type 1) Cone (Type 2) Cone-split (Type 3) Vertical (Type 4) Shear (Type 5) Edge Fracture (Type 6) Pointed

Field Test Data

Specimen Type Selection : Cylinder

Set Number :B
Date Sampled :03/31/2026
Sampled By :Balu Mylabathula
Contractor :CONLAN
Truck Number :11
Time Batched :23:36
Location of Placement :N/A
Number of samples cast :5
Ambient Temperature (°f) :N/A
Slump (in.) :6
Water added (gal.) :N/A
Laboratory Number :2026-082
Time Sampled :12:00
Weather Condition :Cloudy
Concrete Supplier :MORGAN
Mix ID :57-89 SOG NA
Quantity of Load (cu. yd.) :10
Sample Cast :10
Specified Strength :4000
Concrete Temperature(°f) :65
Air Content (%) :2.7
Unit Weight (pcf) :147.3

Strength Test Results

Specimen Number Scheduled Test Date Date Tested Age (days) Dia(in.) Area (sq in.) Maximum Loads (lbf) Strength (lbs) % Design Strength Type of Fracture
B1 04/07/2026 04/07/2026 7 3.80 11.34 47522 4190 Infinity Type 2
B2 04/28/2026 04/28/2026 28 3.75 11.04 63505 5750 143.8 Type 5
B3 04/28/2026 04/28/2026 28 3.75 11.04 64115 5810 145.3 Type 3
B4 04/28/2026 04/28/2026 28 3.85 11.64 65357 5610 140.3 Type 2
5 05/26/2026 N/A

UNLESS OTHERWISE SPECIFIED, TESTS WERE PERFORMED IN ACCORDANCE WITH ASTM TEST METHODS C31, C39, C138, C143, C173, AND C1064. FRACTURE TYPE INDICATED BY NUMBER.

(Type 1) Cone (Type 2) Cone-split (Type 3) Vertical (Type 4) Shear (Type 5) Edge Fracture (Type 6) Pointed

Field Test Data

Specimen Type Selection : Cylinder

Set Number :C
Date Sampled :03/31/2026
Sampled By :Balu Mylabathula
Contractor :CONLAN
Truck Number :21
Time Batched :00:26
Location of Placement :N/A
Number of samples cast :5
Ambient Temperature (°f) :N/A
Slump (in.) :5.5
Water added (gal.) :N/A
Laboratory Number :2026-082
Time Sampled :01:00
Weather Condition :Cloudy
Concrete Supplier :MORGAN
Mix ID :57-89 SOG NA
Quantity of Load (cu. yd.) :10
Sample Cast :10
Specified Strength :4000
Concrete Temperature(°f) :66
Air Content (%) :2.2
Unit Weight (pcf) :146.8

Strength Test Results

Specimen Number Scheduled Test Date Date Tested Age (days) Dia(in.) Area (sq in.) Maximum Loads (lbf) Strength (lbs) % Design Strength Type of Fracture
C1 04/07/2026 04/07/2026 7 3.75 11.04 49177 4450 Infinity Type 5
C2 04/28/2026 04/28/2026 28 3.75 11.04 58649 5310 132.8 Type 2
C3 04/28/2026 04/28/2026 28 3.80 11.34 60821 5360 134.0 Type 5
C4 04/28/2026 04/28/2026 28 3.85 11.64 60105 5160 129.0 Type 2
5 05/26/2026 N/A

UNLESS OTHERWISE SPECIFIED, TESTS WERE PERFORMED IN ACCORDANCE WITH ASTM TEST METHODS C31, C39, C138, C143, C173, AND C1064. FRACTURE TYPE INDICATED BY NUMBER.

(Type 1) Cone (Type 2) Cone-split (Type 3) Vertical (Type 4) Shear (Type 5) Edge Fracture (Type 6) Pointed

Field Test Data

Specimen Type Selection : Cylinder

Set Number :D
Date Sampled :03/31/2026
Sampled By :Balu Mylabathula
Contractor :CONBUF
Truck Number :31
Time Batched :01:15
Location of Placement :N/A
Number of samples cast :5
Ambient Temperature (°f) :N/A
Slump (in.) :5.5
Water added (gal.) :N/A
Laboratory Number :2026-082
Time Sampled :01:45
Weather Condition :Cloudy
Concrete Supplier :MORGAN
Mix ID :57-89 SOG NA
Quantity of Load (cu. yd.) :10
Sample Cast :10
Specified Strength :4000
Concrete Temperature(°f) :65
Air Content (%) :1.5
Unit Weight (pcf) :144.6

Strength Test Results

Specimen Number Scheduled Test Date Date Tested Age (days) Dia(in.) Area (sq in.) Maximum Loads (lbf) Strength (lbs) % Design Strength Type of Fracture
D1 04/07/2026 04/07/2026 7 3.80 11.34 49746 4390 Infinity Type 5
D2 04/28/2026 04/28/2026 28 3.75 11.04 Type 2
D3 04/28/2026 04/28/2026 28 3.75 11.04 64067 5800 145.0 Type 5
D4 04/28/2026 04/28/2026 28 3.75 11.04 65186 5900 147.5 Type 3
5 05/26/2026 N/A

UNLESS OTHERWISE SPECIFIED, TESTS WERE PERFORMED IN ACCORDANCE WITH ASTM TEST METHODS C31, C39, C138, C143, C173, AND C1064. FRACTURE TYPE INDICATED BY NUMBER.

(Type 1) Cone (Type 2) Cone-split (Type 3) Vertical (Type 4) Shear (Type 5) Edge Fracture (Type 6) Pointed

Field Test Data

Specimen Type Selection : Cylinder

Set Number :E
Date Sampled :03/31/2026
Sampled By :Balu Mylabathula
Contractor :N/A
Truck Number :41
Time Batched :02:06
Location of Placement :N/A
Number of samples cast :5
Ambient Temperature (°f) :N/A
Slump (in.) :4.5
Water added (gal.) :N/A
Laboratory Number :2026-082
Time Sampled :02:15
Weather Condition :Cloudy
Concrete Supplier :N/A
Mix ID :57-89 SOG NA
Quantity of Load (cu. yd.) :10
Sample Cast :10
Specified Strength :4000
Concrete Temperature(°f) :68
Air Content (%) :1.7
Unit Weight (pcf) :148.9

Strength Test Results

Specimen Number Scheduled Test Date Date Tested Age (days) Dia(in.) Area (sq in.) Maximum Loads (lbf) Strength (lbs) % Design Strength Type of Fracture
E1 04/07/2026 04/07/2026 7 3.75 11.04 51731 4690 Infinity Type 2
E2 04/28/2026 04/28/2026 28 3.70 10.75 64234 5980 149.5 Type 3
E3 04/28/2026 04/28/2026 28 3.80 11.34 70090 6180 154.5 Type 2
E4 04/28/2026 04/28/2026 28 3.80 11.34 62467 5510 137.8 Type 5
E5 05/26/2026 N/A

UNLESS OTHERWISE SPECIFIED, TESTS WERE PERFORMED IN ACCORDANCE WITH ASTM TEST METHODS C31, C39, C138, C143, C173, AND C1064. FRACTURE TYPE INDICATED BY NUMBER.

(Type 1) Cone (Type 2) Cone-split (Type 3) Vertical (Type 4) Shear (Type 5) Edge Fracture (Type 6) Pointed

Field Test Data

Specimen Type Selection : Cylinder

Set Number :F
Date Sampled :03/31/2026
Sampled By :Balu Mylabathula
Contractor :N/A
Truck Number :51
Time Batched :03:02
Location of Placement :N/A
Number of samples cast :5
Ambient Temperature (°f) :N/A
Slump (in.) :5
Water added (gal.) :N/A
Laboratory Number :2026-082
Time Sampled :03:18
Weather Condition :Cloudy
Concrete Supplier :N/A
Mix ID :57-89 SOG NA
Quantity of Load (cu. yd.) :10
Sample Cast :10
Specified Strength :4000
Concrete Temperature(°f) :66
Air Content (%) :1.7
Unit Weight (pcf) :145.6

Strength Test Results

Specimen Number Scheduled Test Date Date Tested Age (days) Dia(in.) Area (sq in.) Maximum Loads (lbf) Strength (lbs) % Design Strength Type of Fracture
F1 04/07/2026 04/07/2026 7 3.85 11.64 53280 4580 Infinity Type 2
F2 04/28/2026 04/28/2026 28 3.75 11.04 66227 6000 150.0 Type 5
F3 04/28/2026 04/27/2026 27 3.70 10.75 68580 6380 159.5 Type 2
F4 04/28/2026 04/28/2026 28 3.65 10.46 67336 6440 161.0 Type 5
5 05/26/2026 N/A

UNLESS OTHERWISE SPECIFIED, TESTS WERE PERFORMED IN ACCORDANCE WITH ASTM TEST METHODS C31, C39, C138, C143, C173, AND C1064. FRACTURE TYPE INDICATED BY NUMBER.

(Type 1) Cone (Type 2) Cone-split (Type 3) Vertical (Type 4) Shear (Type 5) Edge Fracture (Type 6) Pointed

Field Test Data

Specimen Type Selection : Cylinder

Set Number :G
Date Sampled :03/31/2026
Sampled By :Balu Mylabathula
Contractor :N/A
Truck Number :61
Time Batched :03:54
Location of Placement :N/A
Number of samples cast :5
Ambient Temperature (°f) :N/A
Slump (in.) :6
Water added (gal.) :N/A
Laboratory Number :2026-082
Time Sampled :04:
Weather Condition :Cloudy
Concrete Supplier :N/A
Mix ID :57-89 SOG NA
Quantity of Load (cu. yd.) :10
Sample Cast :10
Specified Strength :4000
Concrete Temperature(°f) :65
Air Content (%) :2
Unit Weight (pcf) :144.3

Strength Test Results

Specimen Number Scheduled Test Date Date Tested Age (days) Dia(in.) Area (sq in.) Maximum Loads (lbf) Strength (lbs) % Design Strength Type of Fracture
G1 04/07/2026 04/07/2026 7 3.60 10.18 50692 4980 Infinity Type 5
G2 04/28/2026 04/28/2026 28 3.65 10.46 61707 5900 147.5 Type 2
G3 04/28/2026 04/28/2026 28 3.75 11.04 63077 5710 142.8 Type 3
G4 04/28/2026 04/28/2026 28 3.80 11.34 62919 5550 138.8 Type 2
5 05/26/2026 N/A

UNLESS OTHERWISE SPECIFIED, TESTS WERE PERFORMED IN ACCORDANCE WITH ASTM TEST METHODS C31, C39, C138, C143, C173, AND C1064. FRACTURE TYPE INDICATED BY NUMBER.

(Type 1) Cone (Type 2) Cone-split (Type 3) Vertical (Type 4) Shear (Type 5) Edge Fracture (Type 6) Pointed

Field Test Data

Specimen Type Selection : Cylinder

Set Number :H
Date Sampled :03/31/2026
Sampled By :Balu Mylabathula
Contractor :N/A
Truck Number :71
Time Batched :04:42
Location of Placement :N/A
Number of samples cast :5
Ambient Temperature (°f) :N/A
Slump (in.) :6
Water added (gal.) :N/A
Laboratory Number :2026-082
Time Sampled :05:
Weather Condition :Cloudy
Concrete Supplier :N/A
Mix ID :57-89 SOG NA
Quantity of Load (cu. yd.) :10
Sample Cast :10
Specified Strength :4000
Concrete Temperature(°f) :68
Air Content (%) :1.7
Unit Weight (pcf) :144.5

Strength Test Results

Specimen Number Scheduled Test Date Date Tested Age (days) Dia(in.) Area (sq in.) Maximum Loads (lbf) Strength (lbs) % Design Strength Type of Fracture
H1 04/07/2026 04/07/2026 7 3.65 10.46 45837 4380 Infinity Type 1
H2 04/28/2026 04/28/2026 28 3.75 11.04 61849 5600 140.0 Type 2
H3 04/28/2026 04/28/2026 28 3.70 10.75 58930 5480 137.0 Type 3
H4 04/28/2026 04/28/2026 28 3.75 11.04 58930 5340 133.5 Type 2
5 05/26/2026 N/A

UNLESS OTHERWISE SPECIFIED, TESTS WERE PERFORMED IN ACCORDANCE WITH ASTM TEST METHODS C31, C39, C138, C143, C173, AND C1064. FRACTURE TYPE INDICATED BY NUMBER.

(Type 1) Cone (Type 2) Cone-split (Type 3) Vertical (Type 4) Shear (Type 5) Edge Fracture (Type 6) Pointed

Field Test Data

Specimen Type Selection : Cylinder

Set Number :I
Date Sampled :03/31/2026
Sampled By :Balu Mylabathula
Contractor :N/A
Truck Number :81
Time Batched :05:36
Location of Placement :N/A
Number of samples cast :5
Ambient Temperature (°f) :N/A
Slump (in.) :6
Water added (gal.) :N/A
Laboratory Number :2026-082
Time Sampled :6
Weather Condition :Cloudy
Concrete Supplier :N/A
Mix ID :57-89 SOG NA
Quantity of Load (cu. yd.) :10
Sample Cast :10
Specified Strength :4000
Concrete Temperature(°f) :68
Air Content (%) :1.5
Unit Weight (pcf) :140.6

Strength Test Results

Specimen Number Scheduled Test Date Date Tested Age (days) Dia(in.) Area (sq in.) Maximum Loads (lbf) Strength (lbs) % Design Strength Type of Fracture
I1 04/07/2026 04/07/2026 7 3.75 11.04 51433 4660 Infinity Type 2
I2 04/28/2026 04/28/2026 28 3.65 10.46 65818 6290 157.3 Type 6
I3 04/28/2026 04/28/2026 28 3.75 11.04 65179 5900 147.5 Type 5
I4 04/28/2026 04/28/2026 28 3.70 10.75 63191 5880 147.0 Type 2
5 05/26/2026 N/A

UNLESS OTHERWISE SPECIFIED, TESTS WERE PERFORMED IN ACCORDANCE WITH ASTM TEST METHODS C31, C39, C138, C143, C173, AND C1064. FRACTURE TYPE INDICATED BY NUMBER.

(Type 1) Cone (Type 2) Cone-split (Type 3) Vertical (Type 4) Shear (Type 5) Edge Fracture (Type 6) Pointed

Field Test Data

Specimen Type Selection : Cylinder

Set Number :J
Date Sampled :03/31/2026
Sampled By :Balu Mylabathula
Contractor :N/A
Truck Number :91
Time Batched :06:31
Location of Placement :N/A
Number of samples cast :5
Ambient Temperature (°f) :N/A
Slump (in.) :4
Water added (gal.) :N/A
Laboratory Number :2026-082
Time Sampled :07:
Weather Condition :Cloudy
Concrete Supplier :N/A
Mix ID :57-89 SOG NA
Quantity of Load (cu. yd.) :10
Sample Cast :10
Specified Strength :4000
Concrete Temperature(°f) :65
Air Content (%) :1.2
Unit Weight (pcf) :142.3

Strength Test Results

Specimen Number Scheduled Test Date Date Tested Age (days) Dia(in.) Area (sq in.) Maximum Loads (lbf) Strength (lbs) % Design Strength Type of Fracture
J1 04/07/2026 04/07/2026 7 3.70 10.75 48992 4560 Infinity Type 2
J2 04/28/2026 04/28/2026 28 3.75 11.04 64053 5800 145.0 Type 2
J3 04/28/2026 04/28/2026 28 3.75 11.04 60979 5520 138.0 Type 2
4 04/28/2026 04/28/2026 28 3.75 11.04 62181 5630 140.8 Type 2
5 05/26/2026 N/A

UNLESS OTHERWISE SPECIFIED, TESTS WERE PERFORMED IN ACCORDANCE WITH ASTM TEST METHODS C31, C39, C138, C143, C173, AND C1064. FRACTURE TYPE INDICATED BY NUMBER.

(Type 1) Cone (Type 2) Cone-split (Type 3) Vertical (Type 4) Shear (Type 5) Edge Fracture (Type 6) Pointed

Technician Signature / DateCatherine Lanier, March 31, 2026
Reviewer Name / DateKenneth Mosman, May 25, 2026