- Density Test Report Report ID: 93542
- Edit Download Report
Density Test Report
Date :04/25/2026
Project No :2026C103
Client Company :Artisan
Arrival Time :04/24/2026 08:00
Onsite Hours :03:00
Name of the Project :NW PH 2, UNIT 4
Project Location :Dallas
Weather :Sunny
Departure Time :04/24/2026 11:00
ASEC Technician Name :Sean Willett
Observations/Finding
| Test Date | Test Number | Moisture Content (%) | Dry Density (pcf) | Proctor Number | Max. Dry Density (pcf) | Optimum Moisture (%) | Compaction (%) | Specified Compaction (%) | ASTM Test Method | Pass/Fail |
|---|---|---|---|---|---|---|---|---|---|---|
| 04/24/2026 | 1 | 10.4 | 98.7 | Field proctor #6 | 98.0 | 17.2 | 100.7 | 95 | D6938 | Pass |
| Location : | B-15, Elv/Depth :4 feet over pipe | |||||||||
| Comment : | Gauge Serial No. :77-19952 | |||||||||
Technician Signature / DateSean Willett, April 25, 2026
Reviewer Name / DateKenneth Mosman, April 27, 2026