Concrete Test Report

Date :04/02/2026
Project No :2026C115-WO 1
Client Company :WSP
Arrival Time :04/01/2026 21:00
Onsite Hours :12:00
Name of the Project :Lanier Islands Parkway
Project Location :Buford
Weather :cold
Departure Time :04/02/2026 09:00
ASEC Technician Name :Balu Mylabathula

Concrete Placement Information

Location(S): N/A
Testing: 9 Set of concrete specimens (5 per set) were cast during the cast-in-place concrete pour at the above referenced location, in accordance with ASTM C31. The specimen will remain on site for the initial 24-48 hrs curing.
Compliance:

Field placement of concrete appeared to be in accordance with the project specifications (i.e., slump, temperature, etc) (refer to remarks below)

Deviations and/or noncompliances were noted during the field placement (refer to remarks below)

Specimen
Pick Up:
9 Sets of concrete specimens/ 5 specimen per set were picked up & transported to AS Engineering and Consulting LLC (ASEC) for curing and testing in accordance with ASTM C39, C670/1231
Field Curing: Specimen were stored for the initial 24 hours.
Near the poured structure
In an insulated curing box
Other
Remarks:

Field Test Data

Specimen Type Selection : Cylinder

Set Number :A
Date Sampled :04/02/2026
Sampled By :Balu Mylabathula
Contractor :N/A
Truck Number :N/A
Time Batched :N/A
Location of Placement :N/A
Number of samples cast :5
Ambient Temperature (°f) :N/A
Slump (in.) :5.5
Water added (gal.) :N/A
Laboratory Number :2026-088
Time Sampled :00:30
Weather Condition :cold
Concrete Supplier :N/A
Mix ID :57-89 SOG NA
Quantity of Load (cu. yd.) :10
Sample Cast :9
Specified Strength :4000
Concrete Temperature(°f) :68
Air Content (%) :5
Unit Weight (pcf) :143.6

Strength Test Results

Specimen Number Scheduled Test Date Date Tested Age (days) Dia(in.) Area (sq in.) Maximum Loads (lbf) Strength (lbs) % Design Strength Type of Fracture
A1 04/09/2026 04/09/2026 7 3.98 12.41 49557 3990 Infinity Type 2
A2 04/30/2026 04/30/2026 28 3.97 12.38 60270 4870 Infinity Type 2
A3 04/30/2026 04/30/2026 28 3.97 12.38 61581 4970 Infinity Type 5
A4 04/30/2026 04/30/2026 28 3.97 12.38 63246 5110 Infinity Type 3
A5 05/28/2026 N/A

UNLESS OTHERWISE SPECIFIED, TESTS WERE PERFORMED IN ACCORDANCE WITH ASTM TEST METHODS C31, C39, C138, C143, C173, AND C1064. FRACTURE TYPE INDICATED BY NUMBER.

(Type 1) Cone (Type 2) Cone-split (Type 3) Vertical (Type 4) Shear (Type 5) Edge Fracture (Type 6) Pointed

Field Test Data

Specimen Type Selection : Cylinder

Set Number :B
Date Sampled :04/02/2026
Sampled By :Balu Mylabathula
Contractor :N/A
Truck Number :11
Time Batched :N/A
Location of Placement :N/A
Number of samples cast :5
Ambient Temperature (°f) :N/A
Slump (in.) :4.5
Water added (gal.) :N/A
Laboratory Number :2026-088
Time Sampled :N/A
Weather Condition :cold
Concrete Supplier :N/A
Mix ID :57-89 SOG NA
Quantity of Load (cu. yd.) :N/A
Sample Cast :9
Specified Strength :4000
Concrete Temperature(°f) :67
Air Content (%) :3.7
Unit Weight (pcf) :144

Strength Test Results

Specimen Number Scheduled Test Date Date Tested Age (days) Dia(in.) Area (sq in.) Maximum Loads (lbf) Strength (lbs) % Design Strength Type of Fracture
B1 04/09/2026 04/09/2026 7 3.98 12.41 54483 4390 Infinity Type 2
B2 04/30/2026 04/30/2026 28 3.98 12.41 65197 5250 Infinity Type 2
B3 04/30/2026 04/30/2026 28 3.98 12.41 70526 5680 Infinity Type 2
B4 04/30/2026 04/30/2026 28 3.98 12.41 63364 5110 Infinity Type 3
B5 05/28/2026 N/A

UNLESS OTHERWISE SPECIFIED, TESTS WERE PERFORMED IN ACCORDANCE WITH ASTM TEST METHODS C31, C39, C138, C143, C173, AND C1064. FRACTURE TYPE INDICATED BY NUMBER.

(Type 1) Cone (Type 2) Cone-split (Type 3) Vertical (Type 4) Shear (Type 5) Edge Fracture (Type 6) Pointed

Field Test Data

Specimen Type Selection : Cylinder

Set Number :C
Date Sampled :04/02/2026
Sampled By :Balu Mylabathula
Contractor :N/A
Truck Number :N/A
Time Batched :N/A
Location of Placement :N/A
Number of samples cast :5
Ambient Temperature (°f) :N/A
Slump (in.) :6
Water added (gal.) :N/A
Laboratory Number :2026-088
Time Sampled :N/A
Weather Condition :cold
Concrete Supplier :N/A
Mix ID :57-89 SOG NA
Quantity of Load (cu. yd.) :10
Sample Cast :9
Specified Strength :4000
Concrete Temperature(°f) :N/A
Air Content (%) :4
Unit Weight (pcf) :143.2

Strength Test Results

Specimen Number Scheduled Test Date Date Tested Age (days) Dia(in.) Area (sq in.) Maximum Loads (lbf) Strength (lbs) % Design Strength Type of Fracture
C1 04/09/2026 04/09/2026 7 3.97 12.38 46821 3780 Infinity Type 5
C2 04/30/2026 04/30/2026 28 3.97 12.38 63491 5130 Infinity Type 2
C3 04/30/2026 04/30/2026 28 3.97 12.38 60923 4920 Infinity Type 5
C4 04/30/2026 04/30/2026 28 3.97 12.38 60749 4910 Infinity Type 3
C5 05/28/2026 N/A

UNLESS OTHERWISE SPECIFIED, TESTS WERE PERFORMED IN ACCORDANCE WITH ASTM TEST METHODS C31, C39, C138, C143, C173, AND C1064. FRACTURE TYPE INDICATED BY NUMBER.

(Type 1) Cone (Type 2) Cone-split (Type 3) Vertical (Type 4) Shear (Type 5) Edge Fracture (Type 6) Pointed

Field Test Data

Specimen Type Selection : Cylinder

Set Number :D
Date Sampled :04/02/2026
Sampled By :Balu Mylabathula
Contractor :N/A
Truck Number :N/A
Time Batched :N/A
Location of Placement :N/A
Number of samples cast :5
Ambient Temperature (°f) :N/A
Slump (in.) :6
Water added (gal.) :N/A
Laboratory Number :2026-088
Time Sampled :N/A
Weather Condition :cold
Concrete Supplier :N/A
Mix ID :57-89 SOG NA
Quantity of Load (cu. yd.) :10
Sample Cast :9
Specified Strength :4000
Concrete Temperature(°f) :67
Air Content (%) :4
Unit Weight (pcf) :144.1

Strength Test Results

Specimen Number Scheduled Test Date Date Tested Age (days) Dia(in.) Area (sq in.) Maximum Loads (lbf) Strength (lbs) % Design Strength Type of Fracture
D1 04/09/2026 04/09/2026 7 3.98 12.44 49550 3980 Infinity Type 2
D2 04/30/2026 04/30/2026 28 3.98 12.44 62031 4990 Infinity Type 2
D3 04/30/2026 04/30/2026 28 3.98 12.44 67434 5420 Infinity Type 3
D4 04/30/2026 04/30/2026 28 3.98 12.44 64978 5220 Infinity Type 3
D5 05/28/2026 N/A

UNLESS OTHERWISE SPECIFIED, TESTS WERE PERFORMED IN ACCORDANCE WITH ASTM TEST METHODS C31, C39, C138, C143, C173, AND C1064. FRACTURE TYPE INDICATED BY NUMBER.

(Type 1) Cone (Type 2) Cone-split (Type 3) Vertical (Type 4) Shear (Type 5) Edge Fracture (Type 6) Pointed

Field Test Data

Specimen Type Selection : Cylinder

Set Number :E
Date Sampled :04/02/2026
Sampled By :Balu Mylabathula
Contractor :N/A
Truck Number :N/A
Time Batched :N/A
Location of Placement :N/A
Number of samples cast :5
Ambient Temperature (°f) :N/A
Slump (in.) :5.5
Water added (gal.) :N/A
Laboratory Number :2026-088
Time Sampled :N/A
Weather Condition :cold
Concrete Supplier :N/A
Mix ID :57-89 SOG NA
Quantity of Load (cu. yd.) :10
Sample Cast :9
Specified Strength :4000
Concrete Temperature(°f) :68
Air Content (%) :5
Unit Weight (pcf) :142.1

Strength Test Results

Specimen Number Scheduled Test Date Date Tested Age (days) Dia(in.) Area (sq in.) Maximum Loads (lbf) Strength (lbs) % Design Strength Type of Fracture
E1 04/09/2026 04/09/2026 7 3.97 12.38 51280 4140 Infinity Type 5
E2 04/30/2026 04/30/2026 28 3.97 12.38 69990 5650 Infinity Type 2
E3 04/30/2026 04/30/2026 28 3.97 12.38 56364 4550 Infinity Type 2
E4 04/30/2026 04/30/2026 28 3.97 12.38 63543 5130 Infinity Type 2
E5 05/28/2026 N/A

UNLESS OTHERWISE SPECIFIED, TESTS WERE PERFORMED IN ACCORDANCE WITH ASTM TEST METHODS C31, C39, C138, C143, C173, AND C1064. FRACTURE TYPE INDICATED BY NUMBER.

(Type 1) Cone (Type 2) Cone-split (Type 3) Vertical (Type 4) Shear (Type 5) Edge Fracture (Type 6) Pointed

Field Test Data

Specimen Type Selection : Cylinder

Set Number :F
Date Sampled :04/02/2026
Sampled By :Balu Mylabathula
Contractor :N/A
Truck Number :N/A
Time Batched :N/A
Location of Placement :N/A
Number of samples cast :5
Ambient Temperature (°f) :N/A
Slump (in.) :4
Water added (gal.) :N/A
Laboratory Number :2026-088
Time Sampled :N/A
Weather Condition :cold
Concrete Supplier :N/A
Mix ID :57-89 SOG NA
Quantity of Load (cu. yd.) :10
Sample Cast :9
Specified Strength :4000
Concrete Temperature(°f) :68
Air Content (%) :3.2
Unit Weight (pcf) :145

Strength Test Results

Specimen Number Scheduled Test Date Date Tested Age (days) Dia(in.) Area (sq in.) Maximum Loads (lbf) Strength (lbs) % Design Strength Type of Fracture
F1 04/09/2026 04/09/2026 7 3.97 12.38 48664 3930 Infinity Type 2
F2 04/30/2026 04/30/2026 28 3.97 12.38 60278 4870 Infinity Type 2
F3 04/30/2026 04/30/2026 28 3.97 12.38 65032 5250 Infinity Type 3
F4 04/30/2026 04/30/2026 28 3.97 12.38 Type 2
F5 05/28/2026 05/28/2026 56

UNLESS OTHERWISE SPECIFIED, TESTS WERE PERFORMED IN ACCORDANCE WITH ASTM TEST METHODS C31, C39, C138, C143, C173, AND C1064. FRACTURE TYPE INDICATED BY NUMBER.

(Type 1) Cone (Type 2) Cone-split (Type 3) Vertical (Type 4) Shear (Type 5) Edge Fracture (Type 6) Pointed

Field Test Data

Specimen Type Selection : Cylinder

Set Number :G
Date Sampled :04/02/2026
Sampled By :Balu Mylabathula
Contractor :N/A
Truck Number :N/A
Time Batched :N/A
Location of Placement :N/A
Number of samples cast :5
Ambient Temperature (°f) :N/A
Slump (in.) :5.5
Water added (gal.) :N/A
Laboratory Number :2026-088
Time Sampled :N/A
Weather Condition :cold
Concrete Supplier :N/A
Mix ID :57-89 SOG NA
Quantity of Load (cu. yd.) :10
Sample Cast :9
Specified Strength :4000
Concrete Temperature(°f) :68
Air Content (%) :4
Unit Weight (pcf) :143

Strength Test Results

Specimen Number Scheduled Test Date Date Tested Age (days) Dia(in.) Area (sq in.) Maximum Loads (lbf) Strength (lbs) % Design Strength Type of Fracture
G1 04/09/2026 04/09/2026 7 3.97 12.38 50774 4100 Infinity Type 5
G2 04/30/2026 04/30/2026 28 3.97 12.38 58225 4700 Infinity Type 5
G3 04/30/2026 04/30/2026 28 3.97 12.38 68275 5510 Infinity Type 3
G4 04/30/2026 04/30/2026 28 3.97 12.38 61766 4990 Infinity Type 2
G5 05/28/2026 05/28/2026 56

UNLESS OTHERWISE SPECIFIED, TESTS WERE PERFORMED IN ACCORDANCE WITH ASTM TEST METHODS C31, C39, C138, C143, C173, AND C1064. FRACTURE TYPE INDICATED BY NUMBER.

(Type 1) Cone (Type 2) Cone-split (Type 3) Vertical (Type 4) Shear (Type 5) Edge Fracture (Type 6) Pointed

Field Test Data

Specimen Type Selection : Cylinder

Set Number :H
Date Sampled :04/02/2026
Sampled By :Balu Mylabathula
Contractor :N/A
Truck Number :N/A
Time Batched :N/A
Location of Placement :N/A
Number of samples cast :5
Ambient Temperature (°f) :N/A
Slump (in.) :4.5
Water added (gal.) :N/A
Laboratory Number :2026-088
Time Sampled :N/A
Weather Condition :cold
Concrete Supplier :N/A
Mix ID :57-89 SOG NA
Quantity of Load (cu. yd.) :10
Sample Cast :9
Specified Strength :4000
Concrete Temperature(°f) :69
Air Content (%) :3.2
Unit Weight (pcf) :145.1

Strength Test Results

Specimen Number Scheduled Test Date Date Tested Age (days) Dia(in.) Area (sq in.) Maximum Loads (lbf) Strength (lbs) % Design Strength Type of Fracture
H1 04/09/2026 04/09/2026 7 3.96 12.35 51020 4130 Infinity Type 2
H2 04/30/2026 04/30/2026 28 3.96 12.35 64953 5260 Infinity Type 2
H3 04/30/2026 04/30/2026 28 3.96 12.35 71882 5820 Infinity Type 3
H4 04/30/2026 04/30/2026 28 3.96 12.35 70784 5730 Infinity Type 2
H5 05/28/2026 05/28/2026 56

UNLESS OTHERWISE SPECIFIED, TESTS WERE PERFORMED IN ACCORDANCE WITH ASTM TEST METHODS C31, C39, C138, C143, C173, AND C1064. FRACTURE TYPE INDICATED BY NUMBER.

(Type 1) Cone (Type 2) Cone-split (Type 3) Vertical (Type 4) Shear (Type 5) Edge Fracture (Type 6) Pointed

Field Test Data

Specimen Type Selection : Cylinder

Set Number :I
Date Sampled :04/02/2026
Sampled By :Balu Mylabathula
Contractor :N/A
Truck Number :N/A
Time Batched :N/A
Location of Placement :N/A
Number of samples cast :5
Ambient Temperature (°f) :N/A
Slump (in.) :6
Water added (gal.) :N/A
Laboratory Number :2026-088
Time Sampled :N/A
Weather Condition :cold
Concrete Supplier :N/A
Mix ID :57-89 SOG NA
Quantity of Load (cu. yd.) :10
Sample Cast :9
Specified Strength :4000
Concrete Temperature(°f) :66
Air Content (%) :3
Unit Weight (pcf) :146.3

Strength Test Results

Specimen Number Scheduled Test Date Date Tested Age (days) Dia(in.) Area (sq in.) Maximum Loads (lbf) Strength (lbs) % Design Strength Type of Fracture
I1 04/09/2026 04/09/2026 7 3.98 12.41 50081 4040 Infinity Type 2
I2 04/30/2026 04/30/2026 28 3.98 12.41 58622 4720 Infinity Type 2
I3 04/30/2026 04/30/2026 28 3.98 12.41 69454 5600 Infinity Type 2
I4 04/30/2026 04/30/2026 28 3.98 12.41 64382 5190 Infinity Type 3
I5 05/28/2026 N/A

UNLESS OTHERWISE SPECIFIED, TESTS WERE PERFORMED IN ACCORDANCE WITH ASTM TEST METHODS C31, C39, C138, C143, C173, AND C1064. FRACTURE TYPE INDICATED BY NUMBER.

(Type 1) Cone (Type 2) Cone-split (Type 3) Vertical (Type 4) Shear (Type 5) Edge Fracture (Type 6) Pointed

Technician Signature / DateCatherine Lanier, April 2, 2026
Reviewer Name / DateKenneth Mosman, May 25, 2026