Concrete Test Report

Date :04/24/2026
Project No :2025C214
Client Company :Artisan
Arrival Time :04/24/2026 07:00
Onsite Hours :05:30
Name of the Project :NW Unit 4 BRIDGE (Materials Testing)
Project Location :Dallas
Weather :
Departure Time :04/24/2026 12:30
ASEC Technician Name :Charles Bolling

Concrete Placement Information

Location(S): N/A
Testing: 3 Set of concrete specimens (6 per set) were cast during the cast-in-place concrete pour at the above referenced location, in accordance with ASTM C31. The specimen will remain on site for the initial 24-48 hrs curing.
Compliance:

Field placement of concrete appeared to be in accordance with the project specifications (i.e., slump, temperature, etc) (refer to remarks below)

Deviations and/or noncompliances were noted during the field placement (refer to remarks below)

Specimen
Pick Up:
3 Sets of concrete specimens/ 6 specimen per set were picked up & transported to AS Engineering and Consulting LLC (ASEC) for curing and testing in accordance with ASTM C39, C670/1231
Field Curing: Specimen were stored for the initial 24 hours.
Near the poured structure
In an insulated curing box
Other
Remarks:

Field Test Data

Specimen Type Selection : Cylinder

Set Number :A
Date Sampled :04/24/2026
Sampled By :Charles Bolling
Contractor :N/A
Truck Number :320
Time Batched :07:15
Location of Placement :WALL
Number of samples cast :6
Ambient Temperature (°f) :59
Slump (in.) :4
Water added (gal.) :N/A
Laboratory Number :2026-128
Time Sampled :08:20
Weather Condition :N/A
Concrete Supplier :ERNST CONCRETE40CA6
Mix ID :40CA6
Quantity of Load (cu. yd.) :9
Sample Cast :3
Specified Strength :4000AEA
Concrete Temperature(°f) :70
Air Content (%) :3
Unit Weight (pcf) :148.56

Strength Test Results

Specimen Number Scheduled Test Date Date Tested Age (days) Dia(in.) Area (sq in.) Maximum Loads (lbf) Strength (lbs) % Design Strength Type of Fracture
1 04/28/2026 04/28/2026 4 3.97 12.38 43458 3510 Infinity Type 6
2 05/01/2026 05/05/2026 11 3.98 12.41 42597 3430 Infinity Type 2
3 05/22/2026 05/22/2026 28 3.98 12.41 55639 4480 Infinity Type 5
4 05/22/2026 05/22/2026 28 3.98 12.41 54799 4420 Infinity Type 5
5 05/22/2026 05/22/2026 28 3.98 12.41 49579 4000 Infinity Type 5
6 06/19/2026 N/A

UNLESS OTHERWISE SPECIFIED, TESTS WERE PERFORMED IN ACCORDANCE WITH ASTM TEST METHODS C31, C39, C138, C143, C173, AND C1064. FRACTURE TYPE INDICATED BY NUMBER.

(Type 1) Cone (Type 2) Cone-split (Type 3) Vertical (Type 4) Shear (Type 5) Edge Fracture (Type 6) Pointed

Field Test Data

Specimen Type Selection : Cylinder

Set Number :B
Date Sampled :04/24/2026
Sampled By :Charles Bolling
Contractor :REINFORCED WALL SYSTEM LLC
Truck Number :317
Time Batched :07:56
Location of Placement :WALL
Number of samples cast :6
Ambient Temperature (°f) :62
Slump (in.) :6
Water added (gal.) :N/A
Laboratory Number :2026-128
Time Sampled :09:45
Weather Condition :N/A
Concrete Supplier :ERNST CONCRETE
Mix ID :40CA6
Quantity of Load (cu. yd.) :9
Sample Cast :3
Specified Strength :4000
Concrete Temperature(°f) :70
Air Content (%) :3.5
Unit Weight (pcf) :146.4

Strength Test Results

Specimen Number Scheduled Test Date Date Tested Age (days) Dia(in.) Area (sq in.) Maximum Loads (lbf) Strength (lbs) % Design Strength Type of Fracture
1 04/28/2026 04/28/2026 4 3.98 12.41 44723 3600 Infinity Type 6
2 05/01/2026 05/01/2026 7 3.97 12.38 48505 3920 Infinity Type 5
3 05/22/2026 05/22/2026 28 3.98 12.41 59951 4830 Infinity Type 2
4 05/22/2026 05/22/2026 28 3.98 12.41 61608 4960 Infinity Type 6
5 05/22/2026 05/22/2026 28 3.98 12.41 59991 4830 Infinity Type 2

UNLESS OTHERWISE SPECIFIED, TESTS WERE PERFORMED IN ACCORDANCE WITH ASTM TEST METHODS C31, C39, C138, C143, C173, AND C1064. FRACTURE TYPE INDICATED BY NUMBER.

(Type 1) Cone (Type 2) Cone-split (Type 3) Vertical (Type 4) Shear (Type 5) Edge Fracture (Type 6) Pointed

Field Test Data

Specimen Type Selection : Cylinder

Set Number :C
Date Sampled :04/24/2026
Sampled By :Charles Bolling
Contractor :N/A
Truck Number :320
Time Batched :09:50
Location of Placement :WALL
Number of samples cast :6
Ambient Temperature (°f) :72
Slump (in.) :3.5
Water added (gal.) :N/A
Laboratory Number :2026-128
Time Sampled :11:45
Weather Condition :N/A
Concrete Supplier :ERNST CONCRETE
Mix ID :40CA6
Quantity of Load (cu. yd.) :9
Sample Cast :3
Specified Strength :N/A
Concrete Temperature(°f) :73
Air Content (%) :3.2
Unit Weight (pcf) :148.0

Strength Test Results

Specimen Number Scheduled Test Date Date Tested Age (days) Dia(in.) Area (sq in.) Maximum Loads (lbf) Strength (lbs) % Design Strength Type of Fracture
1 04/28/2026 04/28/2026 4 3.97 12.38 42598 3440 Infinity Type 5
2 05/01/2026 05/05/2026 11 3.97 12.38 42963 3470 Infinity Type 3
3 05/22/2026 05/22/2026 28 3.98 12.41

UNLESS OTHERWISE SPECIFIED, TESTS WERE PERFORMED IN ACCORDANCE WITH ASTM TEST METHODS C31, C39, C138, C143, C173, AND C1064. FRACTURE TYPE INDICATED BY NUMBER.

(Type 1) Cone (Type 2) Cone-split (Type 3) Vertical (Type 4) Shear (Type 5) Edge Fracture (Type 6) Pointed

Technician Signature / DateCatherine Lanier, April 24, 2026
Reviewer Name / DateKenneth Mosman, May 28, 2026