Concrete Test Report

Date :05/21/2026
Project No :2025C214
Client Company :Artisan
Arrival Time :05/14/2026
Onsite Hours :
Name of the Project :NW Unit 4 BRIDGE (Materials Testing)
Project Location :Dallas
Weather :
Departure Time :
ASEC Technician Name :Charles Bolling

Concrete Placement Information

Location(S): N/A
Testing: 8 Set of concrete specimens (5 per set) were cast during the cast-in-place concrete pour at the above referenced location, in accordance with ASTM C31. The specimen will remain on site for the initial 24-48 hrs curing.
Compliance:

Field placement of concrete appeared to be in accordance with the project specifications (i.e., slump, temperature, etc) (refer to remarks below)

Deviations and/or noncompliances were noted during the field placement (refer to remarks below)

Specimen
Pick Up:
8 Sets of concrete specimens/ 5 specimen per set were picked up & transported to AS Engineering and Consulting LLC (ASEC) for curing and testing in accordance with ASTM C39, C670/1231
Field Curing: Specimen were stored for the initial 24 hours.
Near the poured structure
In an insulated curing box
Other
Remarks:

Field Test Data

Specimen Type Selection : Cylinder

Set Number :A
Date Sampled :05/14/2026
Sampled By :Charles Bolling
Contractor :N/A
Truck Number :N/A
Time Batched :N/A
Location of Placement :N/A
Number of samples cast :5
Ambient Temperature (°f) :N/A
Slump (in.) :N/A
Water added (gal.) :N/A
Laboratory Number :2026-149
Time Sampled :N/A
Weather Condition :N/A
Concrete Supplier :N/A
Mix ID :N/A
Quantity of Load (cu. yd.) :N/A
Sample Cast :8
Specified Strength :N/A
Concrete Temperature(°f) :N/A
Air Content (%) :N/A
Unit Weight (pcf) :N/A

Strength Test Results

Specimen Number Scheduled Test Date Date Tested Age (days) Dia(in.) Area (sq in.) Maximum Loads (lbf) Strength (lbs) % Design Strength Type of Fracture
1 05/21/2026 05/21/2026 7 3.98 12.41 41205 3320 Infinity Type 5
2 06/11/2026 N/A
3 06/11/2026 N/A
4 06/11/2026 N/A
5 07/09/2026 N/A

UNLESS OTHERWISE SPECIFIED, TESTS WERE PERFORMED IN ACCORDANCE WITH ASTM TEST METHODS C31, C39, C138, C143, C173, AND C1064. FRACTURE TYPE INDICATED BY NUMBER.

(Type 1) Cone (Type 2) Cone-split (Type 3) Vertical (Type 4) Shear (Type 5) Edge Fracture (Type 6) Pointed

Field Test Data

Specimen Type Selection : Cylinder

Set Number :B
Date Sampled :05/14/2026
Sampled By :Charles Bolling
Contractor :N/A
Truck Number :N/A
Time Batched :N/A
Location of Placement :N/A
Number of samples cast :5
Ambient Temperature (°f) :N/A
Slump (in.) :N/A
Water added (gal.) :N/A
Laboratory Number :2026-149
Time Sampled :N/A
Weather Condition :N/A
Concrete Supplier :N/A
Mix ID :N/A
Quantity of Load (cu. yd.) :N/A
Sample Cast :8
Specified Strength :N/A
Concrete Temperature(°f) :N/A
Air Content (%) :N/A
Unit Weight (pcf) :N/A

Strength Test Results

Specimen Number Scheduled Test Date Date Tested Age (days) Dia(in.) Area (sq in.) Maximum Loads (lbf) Strength (lbs) % Design Strength Type of Fracture
1 05/21/2026 05/21/2026 7 3.98 12.41 44112 3550 Infinity Type 5
2 06/11/2026 N/A
3 06/11/2026 N/A
4 06/11/2026 N/A
5 07/09/2026 N/A

UNLESS OTHERWISE SPECIFIED, TESTS WERE PERFORMED IN ACCORDANCE WITH ASTM TEST METHODS C31, C39, C138, C143, C173, AND C1064. FRACTURE TYPE INDICATED BY NUMBER.

(Type 1) Cone (Type 2) Cone-split (Type 3) Vertical (Type 4) Shear (Type 5) Edge Fracture (Type 6) Pointed

Field Test Data

Specimen Type Selection : Cylinder

Set Number :C
Date Sampled :05/14/2026
Sampled By :Charles Bolling
Contractor :N/A
Truck Number :N/A
Time Batched :N/A
Location of Placement :N/A
Number of samples cast :5
Ambient Temperature (°f) :N/A
Slump (in.) :N/A
Water added (gal.) :N/A
Laboratory Number :2026-149
Time Sampled :N/A
Weather Condition :N/A
Concrete Supplier :N/A
Mix ID :N/A
Quantity of Load (cu. yd.) :N/A
Sample Cast :8
Specified Strength :N/A
Concrete Temperature(°f) :N/A
Air Content (%) :N/A
Unit Weight (pcf) :N/A

Strength Test Results

Specimen Number Scheduled Test Date Date Tested Age (days) Dia(in.) Area (sq in.) Maximum Loads (lbf) Strength (lbs) % Design Strength Type of Fracture
1 05/21/2026 05/21/2026 7 3.98 12.41 44815 3610 Infinity Type 6
2 06/11/2026 N/A
3 06/11/2026 N/A
4 06/11/2026 N/A
5 07/09/2026 N/A

UNLESS OTHERWISE SPECIFIED, TESTS WERE PERFORMED IN ACCORDANCE WITH ASTM TEST METHODS C31, C39, C138, C143, C173, AND C1064. FRACTURE TYPE INDICATED BY NUMBER.

(Type 1) Cone (Type 2) Cone-split (Type 3) Vertical (Type 4) Shear (Type 5) Edge Fracture (Type 6) Pointed

Field Test Data

Specimen Type Selection : Cylinder

Set Number :D
Date Sampled :05/14/2026
Sampled By :Charles Bolling
Contractor :N/A
Truck Number :N/A
Time Batched :N/A
Location of Placement :N/A
Number of samples cast :5
Ambient Temperature (°f) :N/A
Slump (in.) :N/A
Water added (gal.) :N/A
Laboratory Number :2026-149
Time Sampled :N/A
Weather Condition :N/A
Concrete Supplier :N/A
Mix ID :N/A
Quantity of Load (cu. yd.) :N/A
Sample Cast :8
Specified Strength :N/A
Concrete Temperature(°f) :N/A
Air Content (%) :N/A
Unit Weight (pcf) :N/A

Strength Test Results

Specimen Number Scheduled Test Date Date Tested Age (days) Dia(in.) Area (sq in.) Maximum Loads (lbf) Strength (lbs) % Design Strength Type of Fracture
1 05/21/2026 05/21/2026 7 3.98 12.41 44635 3600 Infinity Type 5
2 06/11/2026 N/A
3 06/11/2026 N/A
4 06/11/2026 N/A
5 07/09/2026 N/A

UNLESS OTHERWISE SPECIFIED, TESTS WERE PERFORMED IN ACCORDANCE WITH ASTM TEST METHODS C31, C39, C138, C143, C173, AND C1064. FRACTURE TYPE INDICATED BY NUMBER.

(Type 1) Cone (Type 2) Cone-split (Type 3) Vertical (Type 4) Shear (Type 5) Edge Fracture (Type 6) Pointed

Field Test Data

Specimen Type Selection : Cylinder

Set Number :E
Date Sampled :05/14/2026
Sampled By :Charles Bolling
Contractor :N/A
Truck Number :N/A
Time Batched :N/A
Location of Placement :N/A
Number of samples cast :5
Ambient Temperature (°f) :N/A
Slump (in.) :N/A
Water added (gal.) :N/A
Laboratory Number :2026-149
Time Sampled :N/A
Weather Condition :N/A
Concrete Supplier :N/A
Mix ID :N/A
Quantity of Load (cu. yd.) :N/A
Sample Cast :8
Specified Strength :N/A
Concrete Temperature(°f) :N/A
Air Content (%) :N/A
Unit Weight (pcf) :N/A

Strength Test Results

Specimen Number Scheduled Test Date Date Tested Age (days) Dia(in.) Area (sq in.) Maximum Loads (lbf) Strength (lbs) % Design Strength Type of Fracture
1 05/21/2026 05/21/2026 7 3.98 12.41 44090 3550 Infinity Type 3
2 06/11/2026 N/A
3 06/11/2026 N/A
4 06/11/2026 N/A
5 07/09/2026 N/A

UNLESS OTHERWISE SPECIFIED, TESTS WERE PERFORMED IN ACCORDANCE WITH ASTM TEST METHODS C31, C39, C138, C143, C173, AND C1064. FRACTURE TYPE INDICATED BY NUMBER.

(Type 1) Cone (Type 2) Cone-split (Type 3) Vertical (Type 4) Shear (Type 5) Edge Fracture (Type 6) Pointed

Field Test Data

Specimen Type Selection : Cylinder

Set Number :F
Date Sampled :05/14/2026
Sampled By :Charles Bolling
Contractor :N/A
Truck Number :N/A
Time Batched :N/A
Location of Placement :N/A
Number of samples cast :5
Ambient Temperature (°f) :N/A
Slump (in.) :N/A
Water added (gal.) :N/A
Laboratory Number :2026-149
Time Sampled :N/A
Weather Condition :N/A
Concrete Supplier :N/A
Mix ID :N/A
Quantity of Load (cu. yd.) :N/A
Sample Cast :8
Specified Strength :N/A
Concrete Temperature(°f) :N/A
Air Content (%) :N/A
Unit Weight (pcf) :N/A

Strength Test Results

Specimen Number Scheduled Test Date Date Tested Age (days) Dia(in.) Area (sq in.) Maximum Loads (lbf) Strength (lbs) % Design Strength Type of Fracture
1 05/21/2026 05/21/2026 7 3.98 12.41 46925 3780 Infinity Type 5
2 06/11/2026 N/A
3 06/11/2026 N/A
4 06/11/2026 N/A
5 07/09/2026 N/A

UNLESS OTHERWISE SPECIFIED, TESTS WERE PERFORMED IN ACCORDANCE WITH ASTM TEST METHODS C31, C39, C138, C143, C173, AND C1064. FRACTURE TYPE INDICATED BY NUMBER.

(Type 1) Cone (Type 2) Cone-split (Type 3) Vertical (Type 4) Shear (Type 5) Edge Fracture (Type 6) Pointed

Field Test Data

Specimen Type Selection : Cylinder

Set Number :G
Date Sampled :05/14/2026
Sampled By :Charles Bolling
Contractor :N/A
Truck Number :N/A
Time Batched :N/A
Location of Placement :N/A
Number of samples cast :5
Ambient Temperature (°f) :N/A
Slump (in.) :N/A
Water added (gal.) :N/A
Laboratory Number :2026-149
Time Sampled :N/A
Weather Condition :N/A
Concrete Supplier :N/A
Mix ID :N/A
Quantity of Load (cu. yd.) :N/A
Sample Cast :8
Specified Strength :N/A
Concrete Temperature(°f) :N/A
Air Content (%) :N/A
Unit Weight (pcf) :N/A

Strength Test Results

Specimen Number Scheduled Test Date Date Tested Age (days) Dia(in.) Area (sq in.) Maximum Loads (lbf) Strength (lbs) % Design Strength Type of Fracture
1 05/21/2026 05/21/2026 7 3.98 12.41 41067 3310 Infinity Type 5
2 06/11/2026 N/A
3 06/11/2026 N/A
4 06/11/2026 N/A
5 07/09/2026 N/A

UNLESS OTHERWISE SPECIFIED, TESTS WERE PERFORMED IN ACCORDANCE WITH ASTM TEST METHODS C31, C39, C138, C143, C173, AND C1064. FRACTURE TYPE INDICATED BY NUMBER.

(Type 1) Cone (Type 2) Cone-split (Type 3) Vertical (Type 4) Shear (Type 5) Edge Fracture (Type 6) Pointed

Field Test Data

Specimen Type Selection : Cylinder

Set Number :H
Date Sampled :05/14/2026
Sampled By :Charles Bolling
Contractor :N/A
Truck Number :N/A
Time Batched :N/A
Location of Placement :N/A
Number of samples cast :5
Ambient Temperature (°f) :N/A
Slump (in.) :N/A
Water added (gal.) :N/A
Laboratory Number :2026-149
Time Sampled :N/A
Weather Condition :N/A
Concrete Supplier :N/A
Mix ID :N/A
Quantity of Load (cu. yd.) :N/A
Sample Cast :8
Specified Strength :N/A
Concrete Temperature(°f) :N/A
Air Content (%) :N/A
Unit Weight (pcf) :N/A

Strength Test Results

Specimen Number Scheduled Test Date Date Tested Age (days) Dia(in.) Area (sq in.) Maximum Loads (lbf) Strength (lbs) % Design Strength Type of Fracture
1 05/21/2026 05/21/2026 7 3.98 12.41 40525 3270 Infinity Type 5
2 06/11/2026 N/A
3 06/11/2026 N/A
4 06/11/2026 N/A
5 07/09/2026 N/A

UNLESS OTHERWISE SPECIFIED, TESTS WERE PERFORMED IN ACCORDANCE WITH ASTM TEST METHODS C31, C39, C138, C143, C173, AND C1064. FRACTURE TYPE INDICATED BY NUMBER.

(Type 1) Cone (Type 2) Cone-split (Type 3) Vertical (Type 4) Shear (Type 5) Edge Fracture (Type 6) Pointed

Technician Signature / DateCatherine Lanier, May 21, 2026
Reviewer Name / DateKenneth Mosman, May 26, 2026